Mitsubishi Electric MELSEC Q Series Reference Manual page 358

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

Device
Item
(S1)+5
Target station No.
(S1)+6
Number of
(S1)+7
resends
Arrival monitoring
(S1)+8
time
(S1)+9
Write data length
(S1)+10
356
Specify the station No. of the target station.
(1)
Station No. specification
When own station is Universal model QCPU: 1 to 120
When own station is other than Universal model QCPUs: 1 to
64
To increase the reliability of data, it is recommended to execute
the instruction with the Execution/Error completion type
((S1)+0) set to "1: With arrival confirmation".
(2)
Group specification
81
to A0
: All stations in group No.1 to 32
H
H
(Setting is available when the execution type is set to "0: No
arrival confirmation" in (S1)+0.)
Group No.1
Group No.2
Group No.32
(3)
All stations
FF
: All stations of the target network No. (Except the own
H
station)
(Setting is available when the execution type is set to "0: With
arrival confirmation" in (S1)+0.)
To specify a group or all stations
• Set "0000
" or "03FF
" for Target station's CPU type (S1+3).
H
H
(
Page 329, Section 9.2.2 (3))
• When the target station is on CC-Link IE Field Network, group
specification cannot be performed.
• To check if data has been properly written in the target station,
check the write destination device on the target station.
Unused
1) For instruction execution
Specify the number of times the instruction is to be resent when
it is not completed within the monitoring time specified in
(S1)+8. (Setting is available when the execution type is set to
"1: With arrival confirmation" in (S1)+0.)
2) At instruction completion
The number of resends executed (result) is stored. (Setting is
valid when the execution type is set to "1: With arrival
confirmation" in (S1)+0.)
Specify the monitoring time required for instruction completion.
(Setting is available when the execution type is set to "1: With arrival
confirmation" in (S1)+0.)
If an instruction is not completed within this time, it will be resent the
number of times specified in (S1)+7.
0: 10 seconds
1 to 32767: 1 to 32767 seconds
Specify the write data size of (S2) to (S2)+n.
When the target station is QCPU/RCPU/LCPU: 1 to 8192 words
*3
When the target station is QnACPU: 1 to 480 words
When specifying 961 words or more, use channel 9 or 10 for the own
station.
Unused
Setting data
81
H
82
H
A0
H
Setting
Setting range
*1
side
1 to 120
81
to A0
User
H
H
FF
H
0
User
0 to 15
User
System
0 to 32767
User
1 to 8192
(1 to 960 when the
User
own station is a
safety CPU)
0
User