No.
Name
SW0000
Link stop/startup
direction
SW0001
to
SW0008
Arrival monitoring time
SW0009
(RIRD/RIWT
instruction)
Number of resends
SW000B
(RIRD/RIWT
instruction)
SW0012
Group specification for
to
link stop/startup
SW0013
SW0020
Module status
Sets station to stop or start cyclic transmission.
00
: Own station
H
01
: All stations
H
02
: Specified station
H
03
: Specified group
H
80
: Own station (forced link startup)
H
81
: All stations (forced link startup)
H
82
: Specified station (forced link startup)
H
83
: Specified group (forced link startup)
H
The cyclic transmission stop/startup can be performed by System link startup
(SB0002) or System link stop (SB0003).
Sets the station No. to stop or start up cyclic transmission when 02
set in Link stop/startup direction (SW0000).
0: Stop or startup not directed
1: Stop or startup directed
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW0001
16 15 14 13 12 11 10
SW0002
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW0003
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW0004
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
SW0005
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
SW0006
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
SW0007
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
SW0008
-
-
-
-
-
Each number in the table represents station No.
Specify the monitoring time required for instruction completion.
If an instruction is not completed within this time, it will be resent the number
of times specified in SW000B.
0: 10 seconds (default)
1 to 360: 1 to 360 seconds
If a value other than the above is specified, 360 seconds will be applied.
Specify the number of times the instruction is to be resent when it is not
completed within the monitoring time specified in SW0009.
0: Not resend (default)
1 to 7: Once to 7 times
If a value other than the above is specified, 7 times will be applied.
Sets the group No. to stop or start up cyclic transmission when 03
set in Link stop/startup direction (SW0000).
0: Stop or startup not directed
1: Stop or startup directed
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW0012
16 15 14 13 12 11 10
SW0013
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
Stores the status of communications between a CC-Link IE Controller
Network module and a CPU module.
0: Normal
A value other than 0: Error code (
Design, Maintenance and Inspection)
Description
9
8
7
6
5
4
3
-
-
- 120 119 118 117 116 115 114 113
9
8
7
6
5
4
3
Each number in the table represents group No.
QCPU User's Manual (Hardware
APPENDICES
Availability
Control
Normal
station
station
or 82
is
H
H
2
1
or 83
is
H
H
2
1
585