(2) Checking data link
The data link status is checked through the CC IE Control diagnostics, but it also can be checked with link special
relay (SB) and link special register (SW). (
(a) Check the data link status of other stations
1.
Link scan time etc., can be checked in SW005A to SW005B and SW0060 to SW0062.
2.
If an error occurs to data link, either of the following link special relays (SB) will be turned ON.
• Baton pass status of each station (SB00A0)
• Cyclic transmission status of each station (SB00B0)
3.
When Baton pass status of each station (SB00A0) is turned ON, the station No. of a station where
an error has occurred is stored in Baton pass status of each station (SW00A0 to SW00A7).
When Cyclic transmission status of each station (SB00B0) is turned ON, the station No. of a
station where an error has occurred is stored in Cyclic transmission status of each station
(SW00B0 to SW00B7).
4.
The details of the cause of an error can be checked with the link special relay (SB) and link special
register (SW) of the station No. for a station where the error has occurred.
No.
SB00A0
Baton pass status of each station
SB00B0
Cyclic transmission status of each station
(b) Checking the data link status of own station
1.
Link scan time etc., can be checked in SW005A to SW005B and SW0060 to SW0062.
2.
If an error occurs to data link, either of the following link special relays (SB) will be turned ON.
• Baton pass status (own station) (SB0047)
• Data link status of own station (SB0049)
3.
The cause of an error is stored in the following link special registers (SW).
• Baton pass status (own station) (SW0047)
• Cause of baton pass interruption (SW0048)
• Cause of data link stop (SW0049)
No.
SB0047
Baton pass status (own station)
SB0049
Data link status of own station
Page 526, Section 10.3)
Description
Description
CHAPTER 8 PROGRAMMING
No.
Description
SW005A
Maximum baton pass station
SW005B
Maximum cyclic transmission station
SW0060
Maximum link scan time
SW0061
Minimum link scan time
SW0062
Current link scan time
SW00A0
to
Baton pass status of each station
SW00A7
SW00B0
to
Cyclic transmission status of each station
SW00B7
No.
Description
SW0047
Baton pass status (own station)
SW0048
Cause of baton pass interruption
SW0049
Cause of data link stop
SW005A
Maximum baton pass station
SW005B
Maximum cyclic transmission station
SW0060
Maximum link scan time
SW0061
Minimum link scan time
SW0062
Current link scan time
8
309