9.9
JP/GP.SEND (Data Transmission to Programmable
Controllers on Other Stations)
This instruction sends data to a programmable controller on another station.
Internal device
Setting
(System, User)
data
Bit
Word
(S1)
—
(S2)
—
(D1)
[Instruction symbol]
[Execution condition]
JP.SEND
GP.SEND
(1) Setting data
Setting data
Jn
Un
(S1)
(S2)
(D1)
*1
Local devices and file registers for each program cannot be used as devices in setting data.
400
Link direct
File
device J\
register
R, ZR
Bit
[Instruction format]
Start contact
Start contact
*1
Network No. of the own station (1 to 239, 254)
254: The network specified in Valid module during other station access
Start I/O number of the own station's CC-Link IE Controller Network module
(00 to FE
: The higher two digits of the 3-digit I/O number)
H
Start device of the own station that stores control data (
Section 9.9 (2))
Start device of the own station that stores send data
The own station's device that is turned on for one scan upon completion of the
instruction
(D1)+1 also turns ON if the instruction execution has failed.
Available devices
Intelligent
function
module device
Word
U\G
JP.SEND
GP.SEND
Description
Constant
Index
register Zn
K, H
—
—
—
Jn
(S1)
(S2)
(D1)
Un
(S1)
(S2)
(D1)
Data type
Binary 16 bits
Page 401,
Device name
Bit
Others
$