Mitsubishi Electric MELSEC Q Series Reference Manual page 404

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

Device
Item
(S1)+1
Completion status
Channel used by
(S1)+2
own station
Target station
(S1)+3
channel
Target station
(S1)+4
network No.
(S1)+5
Target station No.
(S1)+6
Number of
(S1)+7
resends
Arrival monitoring
(S1)+8
time
402
Setting data
The instruction completion status is stored.
0: Normal
Other than 0: Error (
Specify the channel used by the own station. (
Section 9.2.2 (2))
Specify a channel of the target station for storing data.
Specify the network No. of the target station.
1 to 239: Network No.
254: Specify this when 254 has been set in Jn.
Specify the station No. of the target station.
(1)
Station No. specification
When own station is Universal model QCPU: 1 to 120
When own station is other than Universal model QCPUs: 1 to
64
To increase the reliability of data, it is recommended to execute
the instruction with the Execution/Error completion type
((S1)+0) set to "1: With arrival confirmation".
(2)
Group
81
to A0
: All stations in group No.1 to 32
H
H
(Setting is available when the execution type is set to "0: With
arrival confirmation" in (S1)+0.)
Group No.1 ... 81
Group No.2 ... 82
Group No.32 ... A0
(3)
All stations
FF
: All stations of the target network No. (Except the own
H
station)
(Setting is available when the execution type is set to "0: No
arrival confirmation" in (S1)+0.)
To specify a group or all stations
• Stations on the CC-Link IE Field Network cannot be specified as a
group.
Unused
1) For instruction execution
Specify the number of times the instruction is to be resent when
it is not completed within the monitoring time specified in
(S1)+8. (Setting is valid when the execution type is set to "1:
With arrival confirmation" in (S1)+0.)
2) At instruction completion
The number of resends executed (result) is stored. (Setting is
valid when the execution type is set to "1: With arrival
confirmation" in (S1)+0.)
Specify the monitoring time required for instruction completion.
(Setting is available when the execution type is set to "1: With arrival
confirmation" in (S1)+0.)
If an instruction is not completed within this time, it will be resent the
number of times specified in (S1)+7.
0: 10 seconds
1 to 32767: 1 to 32767 seconds
Page 511, Section 10.2)
Page 329,
*3
H
H
H
Setting
Setting range
*1
side
System
1 to 8
User
1 to 8
User
1 to 239
User
254
1 to 120
81
to A0
User
H
H
FF
H
0
User
0 to 15
User
System
0 to 32767
User