Mitsubishi Electric MELSEC Q Series Reference Manual page 169

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

(2) Executing the circuit test
Control station
Powering OFF and ON or resetting the CPU module
starts the test.
During test execution
The MODE and D LINK LEDs flash, and each of the
1 LEDs and each of the
OFF in order (1
2
4
detection of an error, the test is immediately
terminated (error completion).
S
1
1
1
RUN
T.
N
2
2
MODE
O.
4
4
8
8
ERR.
X100
10
1
Test completion
The D LINK LED turns ON.
When completed normally
The MODE LED flashes, and 1, 2, 4 and 8 (
10) LEDs turn OFF.
S
1
1
1
RUN
T.
N
2
2
MODE
O.
4
4
8
8
ERR.
X100
10
1
When failed
The MODE LED flashes, and the ERR.LED and any
one of 1, 2, 4 and 8 (
1 and
1
1
1
S
RUN
T.
N
2
2
MODE
O.
4
4
8
8
ERR.
X100
10
1
Test result?
Set it to online mode, and turn the power OFF and
ON or reset the CPU module.
End
10 LEDs turn ON and
8
1
). Note that, upon
PRM
D LINK
SD
RD
1 and
PRM
D LINK
SD
RD
10) LEDs turn ON.
PRM
D LINK
SD
RD
When failed
When completed normally
CHAPTER 5 PREPARATION AND SETUP
Normal station
Powering OFF and ON or resetting the CPU module
activates the online mode.
During circuit test execution, data link stops on all
stations.
During test execution
The MODE and D LINK LEDs flash, and 1 100 LED
alternates ON and OFF.
S
1
1
1
RUN
T.
N
2
2
MODE
O.
4
4
SD
8
8
ERR.
X100
10
1
While the control station is in online mode, normal
stations operate in online mode.
End
The LED corresponding to the error type turns ON.
Control station duplicated
1
1
Station No. duplicated
2
2
Out-of-range station No. setting exists.
4
4
Reserved station setting error
8
8
(A station set as reserved actually exists.)
10
1
Cable fault
Cable insertion error
Cable disconnection
By the CC IE Control diagnostics, check the
error factor and take corrective actions according to
the troubleshooting.
Page 168, Section 5.6.1 (3)
PRM
D LINK
RD
167
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec qj71gp21-sxMelsec qj71gp21s-sx

Table of Contents