Mitsubishi Electric MELSEC Q Series Reference Manual page 644

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

(c) Example of program replacement
A program used for the following MELSECNET/H system is assumed to be reused.
• Application example in MELSECNET/H (before replacement)
When M152 turns ON, data in D750 to D753 of station No.1 (own station) are sent to logical channel 15 of
all stations (target station).
Station No.1
CPU module
MELSECNET/H
network module
Channel 3
SEND
• Application example in CC-Link IE Controller Network (after replacement)
When M152 turns ON, data in D750 to D753 of station No.1 (own station) are sent to channel 5 of all
stations in group No.1 (target station).
Station No.1
CPU module
CC-Link IE
Controller
Network module
Channel 3
SEND
*1
Group No. setting:
642
Station No.2
MELSECNET/H
CPU module
network module
Program for logical
channel setting
Logical channel 15 (Channel 5)
MELSECNET/H network No.1
Group No.1
Station No.2
CC-Link IE Controller
CPU module
Network module
Channel 5
CC-Link IE Controller Network
network No.1
Page 180, Section 6.2
MELSECNET/H
network module
Logical channel 15 (Channel 1)
RECV
*1
CC-Link IE Controller
Network module
RECV
Channel 5
Station No.10
CPU module
Program for logical
channel setting
RECV
Group No.1
Station No.10
CPU module
RECV
*1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec qj71gp21-sxMelsec qj71gp21s-sx

Table of Contents