IP communications cannot be performed using the IP packet
transfer function.
Before troubleshooting the problem as listed below, execute the IP communication test and take corrective actions
according to the error code. (
If the problem cannot be solved using the IP communication test, execute the actions listed below.
Check item
Is the IP address of the connected Ethernet device correct?
Is the IP address already in use?
Has a communication time over error occurred in the IP
communication test?
Have the routing parameters correctly been set?
Is the network number of the Ethernet device side (the third
octet of the IP address) the same as that of modules and
another Ethernet device? (This applies only when the request
source external device, request destination external device, and
modules between them have the same first and second octets
of the IP address.)
Are settings configured in modules connected to the Ethernet
device correct?
• First and second octets of the IP address
• Subnet mask pattern
• Default router IP address
Are the firewall and proxy server enabled on the Ethernet
device?
Page 113, Section 4.3.3)
Set an IP address meeting the IP address setting rules.
(
Page 109, Section 4.3.2 (1))
• For the Ethernet device, set the IP address different from that of other
devices on the network, such as a CPU module and CC-Link IE
Controller Network module.
• Disconnect the Ethernet device from the line and execute the Ping
command to the IP address of the disconnected Ethernet device. If a
response is received even though the device is disconnected, the IP
address is already in use. Change the IP address.
Check "Relay Network No." in the routing parameters.
• Check and correct the routing parameters. (
4.3.2 (2))
• When the first and second octets of the IP address are the same for
the request source device, request destination device, and modules
between them, set the routing parameters so that the third octet of the
IP address of the Ethernet device is used as "Target Network No.".
Change the network number of the Ethernet device side (the third octet
of the IP address) to the one different from that of modules and another
Ethernet device.
IP address
Ethernet
192.168.
CC-Link
IE Controller
Network
Network No.3
Change the network numbers to those not used for other stations.
Check and correct the settings,
Check and correct the firewall and proxy server settings on the Ethernet
device.
Ex.
Is a response to the Ping command (ICMP echo request) enabled?
CHAPTER 10 TROUBLESHOOTING
Action
3
3
.1
192.168.
.30
192.168.1.1
192.168.1.120
(Automatically assigned)
(Automatically assigned)
Control station
Normal station
(Station No.1)
(Station No.2)
Network No.1
Page 111, Section
2
2
192.168.
.30
192.168.
.1
192.168.1.2
Normal station
(Station No.3)
Network No.2
505
10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec qj71gp21-sxMelsec qj71gp21s-sx

Table of Contents