(1) Intelligent function module interrupt pointer setting
Interrupt (SI) Nos. of the CC-Link IE Controller Network module set in "Interrupt Settings" are linked to interrupt
pointers of the CPU module.
1.
Open the "Intelligent Function Module Interrupt Pointer Setting" window of the programming tool.
Project window
2.
Configure settings with reference to the description below.
3.
Click the
Item
Interrupt Pointer Start No.
PLC Side
Interrupt Pointer Count
Start I/O No.
Intelligent Module
Side
Start SI No.
[PLC Parameter]
[PLC System]
button.
Set the Start No. of the interrupt program (I ).
(Setting range: 50 to 255, Default: None)
Set the number of interrupt conditions.
(Setting range: 1 to 16, Default: None)
Set a start I/O No. of the CC-Link IE Controller Network module.
(Setting range: 0000
Set a start interrupt (SI) No. of the CC-Link IE Controller Network
module.
(Setting range: 0 to 15, Default: None)
CHAPTER 6 PARAMETER SETTING
button
Description
to 0FE0
, Default: None)
H
H
6
227