(10)Checking CPU module status
The CPU module status is checked through the CC IE Control diagnostics, but it also can be checked with link
special relay (SB) and link special register (SW). (
(a) Checking the CPU module status of other stations
1.
Whether the CPU module is in RUN status or STOP status can be checked with the following link
special relay (SB) and link special register (SW).
• CPU RUN status of each station (SB00F0)
• CPU RUN status of each station (SW00F0)
2.
When a continuation error occurs with the CPU module, CPU operation status of each station (2)
(SB0110) is turned ON.
The station No. of the station where a continuation error is occurring is stored in CPU operation
status of each station (2) (SW0110).
3.
When a stop error occurs with the CPU module, CPU operation status of each station (1) (SB0100)
is turned ON.
The station No. of the station where a stop error is occurring is stored in CPU operation status of
each station (1) (SW0100).
No.
SB00F0
CPU RUN status of each station
SB0100
CPU operation status of each station (1)
SB0110
CPU operation status of each station (2)
(b) Checking CPU module status of own station
1.
Whether the CPU module is in RUN status or STOP status can be checked with Own station's CPU
RUN status (SB005B).
2.
When a continuation error occurs with the CPU module, Own station's CPU status (1) (SB004A) is
turned ON.
When a stop error occurs with the CPU module, Own station's CPU status (2) (SB004B) is turned
ON.
3.
The CPU module status can be checked with Own station's CPU status (SW004B).
No.
SB004A
Own station's CPU status (1)
SB004B
Own station's CPU status (2)
SB005B
Own station's CPU RUN status
318
Description
Description
Page 526, Section 10.3)
No.
SW00F0
CPU RUN status of each station
SW0100
CPU operation status of each station (1)
SW0110
CPU operation status of each station (2)
No.
SW004B
Own station's CPU status
Description