98
Commissioning
8.3.2.1
Enable DHCP via "WAGO Ethernet Settings" (without existing IP
address)"
Note Software Compatibility!
Refer to the version of the software specified in "Software Compatibility" in the
Technical Data.
In the delivery state of the head station, the dynamic assignment of the IP
address is active by means of "Dynamic Host Configuration Protocol" (DHCP).
However, if DHCP is not active and you do not have access to your fieldbus node
via an IP address, you can enable DHCP via "WAGO Ethernet Settings" in the
Network tab.
WAGO communication cables or WAGO radio-link adapters can be used for data
communication via the serial service interface.
Do not connect Communication Cable when energized!
To prevent damage to the service interface, do not connect or disconnect
750-920 respectively 750-923 Communication Cable when energized! The
fieldbus coupler/controller must be de-energized!
1.
Using a WAGO Communication cable 750-920 respectively 750-923,
connect your PC with the service interface of the head station of the
fieldbus node.
2.
Start "WAGO Ethernet Settings" program.
Click on [Read] to read in and identify the connected fieldbus node.
3.
Select the Network tab.
4.
Select the option "DHCP" in the field Source.
5.
Click on the [Write] button to apply the settings in the fieldbus node.
6.
The fieldbus node then starts with the new IP address assigned via DHCP.
7.
Then You can use the [Read] button to read out the currently assigned IP
address.
8.
In order to use the IP address permanently, select on "TCP/IP" WBM page
the option "static" in the field Source and apply the settings for "IP
address", "Subnet mask" and "Gateway" from the currently used settings.
9.
Click on the [Write] button to apply the settings.