Table 64: Blink Code Table For The I/O Led Signaling, Error Code 6; Table 65: Blink Code Table For The I/O Led Signaling, Error Code 7; Table 66: Blink Code Table For The I/O Led Signaling, Error Code 8 - WAGO 750-363/0040-0000 Manual

Fc ethernet/ip g4 eco xtr fieldbus coupler ethernet/ip; generation 4; eco; extreme for wago-i/o-system 750
Table of Contents

Advertisement

144 Diagnostics

Table 64: Blink Code Table for the I/O LED Signaling, Error Code 6

Error Code 6: " Configuration error, node configuration"
Error
Argument
1
2
3
4
5
6
7
8
9

Table 65: Blink Code Table for the I/O LED Signaling, Error Code 7

Error Code 7: „Not supported I/O module"
Error
Argument
n

Table 66: Blink Code Table for the I/O LED Signaling, Error Code 8 ... 11

Error Code 8 ... 11: - not used -
Error
Argument
-
Manual
Version 1.0.0
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Error Description
Solution
1. Turn off the power supply of the node.
Invalid MAC ID
2. Replace the head station.
3. Turn on again the power supply of the node.
1. Restart the head station by turning the power supply off and
Ethernet Hardware
initialization error
2. If the error still exists, replace the head station.
1. Restart the head station by turning the power supply off and
TCP/IP initialization
error
2. If the error still exists, replace the head station.
Network configuration
1. Check the settings of DHCP/BootP server or if a static IP
error (no IP Address)
2. Restart the head station by turning the power supply off and
Application protocol
initialization error
3. If the error still exists, replace the head station.
1. Turn off the power supply of the node.
Maximum process
2. Reduce number of I/O modules.
image size exceeded
3. Turn on again the power supply of the node.
1. Change configuration. Use another IP address, which is not
Double IP address in
network
2. Restart the head station by turning the power supply off and
1. Turn off the power supply of the node.
2. Reduce number of I/O modules.
Error when building
3. Restart the head station by turning the power supply off and
the process image
4. If the error still exists, replace the head station.
Error when mapping
the I/O modules to a
1. Check the file „io_config.xml" on the head station.
fieldbus
Error Description
Solution
1. Turn off the power supply for the node.
First not supported
2. Replace the (n+1) I/O module with process data or reduce
I/O module at
position n
3. Turn the power supply on.
Error Description
Solution
Not used
on again.
on again.
address is used.
on again.
yet present in network.
on again.
on again.
the number of I/O modules until the (n+1) I/O module.
-
WAGO-I/O-SYSTEM 750