Supply; Table 24: Technical Data - Supply - WAGO 750-363/0040-0000 Manual

Fc ethernet/ip g4 eco xtr fieldbus coupler ethernet/ip; generation 4; eco; extreme for wago-i/o-system 750
Table of Contents

Advertisement

62
Device Description
4.5.3

Supply

Table 24: Technical Data – Supply
Internal current consumption (5 VDC)
Total current for I/O modules (5 VDC)
Input current
(24 VDC)
Power failure time acc. IEC 61131-2
Supply voltage
System
Field
Derating
for ambient operating temperature
for ambient operating temperature
Efficiency of the power supply
at nominal load
Isolation
Rated impulse voltage
1)
Including residual ripple of 15%
2)
When performing insulation testing, observe the instructions in the manual!
Buffer for system power supply!
The system power supply must be buffered to bridge power outages. As the
power demand depends on the respective node configuration, buffering is not
implemented internally.
To achieve power outages of 1 ms to 10 ms according to IEC61131-2, determine
the buffering appropriate for your node configuration and structure it as an
external circuit.
Manual
Version 1.0.0
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
at nominal load
typ.
under laboratory conditions
−40 °C ... +55 °C
+55 °C ... +70 °C
typ.
WAGO-I/O-SYSTEM 750
350 mA
1700 mA
500 mA
Depending on external buffering
24 VDC via wiring level
(CAGE CLAMP
connection)
®
24 VDC
• incoming via wiring level
(CAGE CLAMP
connection);
®
• outgoing via power jumper contacts
18 V ... 31.2 V (17.4 V ... 31.2 V)
18 V ... 28.8 V (17.4 V ... 28.8 V)
18 V ... 26.4 V (17.4 V ... 26.4 V)
90 %
510 VAC
2)
or 775 VDC power
supply/DIN rail
1 kV
1)
1)
1)