WAGO-I/O-SYSTEM 750
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
4.2.5
Fieldbus Connection
The connection to the fieldbus is made via two RJ-45 plugs, which are connected
to the fieldbus controller via an integrated switch.
The integrated switch works in store-and-forward operation and for each port,
supports the transmission speeds 10/100 Mbit as well as the transmission
modes full and half-duplex and autonegotiation.
The wiring of these plugs corresponds to the specifications
for 100BaseTX, which prescribes a category 5 twisted pair cable as the
connecting cable. Cable types S/UTP (Screened Unshielded Twisted Pair) and
STP (Shielded Twisted Pair) with a maximum segment length of 100 m
(approximately 328.08 feet) can be used.
The socket is arranged physically lower, allowing the coupler to fit in an 80 mm
high enclosure after plug connection.
Figure 29: RJ-45 Connector
Table 17: RJ-45 Connector and RJ-45 Connector Configuration
Contact
1
2
3
4
5
6
7
8
Do not use in telecommunication circuits!
Only use devices equipped with ETHERNET or RJ-45 connectors in LANs.
Never connect these devices with telecommunication networks.
Signal
TD +
Transmit +
TD −
Transmit −
RD +
Receive +
free
free
RD −
Receive −
free
free
Device Description
Manual
Version 1.0.0
57