Storage Media; Table 45: Wbm Page "Miscellaneous - WAGO 750-363/0040-0000 Manual

Fc ethernet/ip g4 eco xtr fieldbus coupler ethernet/ip; generation 4; eco; extreme for wago-i/o-system 750
Table of Contents

Advertisement

120 Configuring via the Web-Based Management System (WBM) WAGO-I/O-SYSTEM 750
These configuration options are stored in non-volatile memory when the
[SUBMIT] button is pressed. Changes to the configuration options take effect
after the next power-on cycle or software reset.

Table 45: WBM Page "Miscellaneous"

Global Settings
Entry
Autoreset on
fatal error
BootP request
before static IP
Non-adaptive local
bus interval
Local bus extension
installed
9.8

Storage Media

Information about the available storage devices and active drives which are
currently mounted within the file system of the device is given on the "Storage
Media" WBM page.
This page will be refreshed every 5 s.
This size information for the storage devices listed below are specified in units of
1 kB with 1 kB = 1024 Byte.
Manual
Version 1.0.0
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Default
Description
Enables an automatic software reset to be conducted
when a system error occurs
Disables an automatic software reset to be conducted
when a system error occurs
Automatically set the static IP address enabled.
For this configuration, the fieldbus coupler/
controller uses a statically configured IP address if the
request via BootP fails.
This process can take a few minutes. With the setting
"DHCP" this function has no effect.
Automatically set the static IP address disabled.
For this configuration, the IP address request via BootP
is repeated in the event of error.
Enables a fixed sampling interval of the local bus and
statically sets the pause time to 14 ms. As a result,
possibly the sampling interval of the local bus is
extended and more computing power is available for the
PLC application.
Enables the dynamic sampling interval of the local bus
(default). The pause time between two local bus cycles is
dynamically adjusted. This shortens the sampling interval
of the local bus and less computing power is available for
the PLC application.
Indicates, that the bus extension (750-627/-628) is
installed.
Indicates, that no bus extension is installed.