WAGO-I/O-SYSTEM 750
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
1.
Based on the handling, which depends on the BootP program set, assign
the required IP address for your fieldbus node.
2.
Enable the query/response mechanism of the BootP protocol based on the
handling, which depends on the BootP program set or e. g. in "WAGO
Ethernet Settings" (Network tab, Source "BootP").
3.
To apply the new IP address, use e.g. a hardware reset to restart your
fieldbus node by interrupt the voltage supply for approx. 2 seconds.
4.
Restart the fieldbus node.
The fieldbus node then starts with the new IP address assigned via BootP.
5.
In order to use the IP address permanently, select in the WBM on "TCP/IP"
WBM page the option "IP configuration source: static" (see chapter "Apply
IP address permanently (option "static ")").
Commissioning 103
Manual
Version 1.0.0