36
System Description
Figure 12: Changing the Fuse and Closing the Fuse Carrier
After changing the fuse, the fuse carrier is pushed back into its original position.
Figure 13: Push Back the Fuse Carrier
3.4.4.3
Fusing External
Field supply only with appropriate fuse protection!
Without overcurrent protection, the electronics can be damaged.
The 24 V input voltage for the field supply is provided with an external fuse with
max. 10 A slow, min. 30 VDC, to be secured.
For the external fusing, the fuse modules of the WAGO series 282, 2006, 281
and 2002 are suitable for this purpose.
Manual
Version 1.0.0
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
WAGO-I/O-SYSTEM 750