Table 60: Blink Code Table For The I/O Led Signaling, Error Code 2 - WAGO 750-363/0040-0000 Manual

Fc ethernet/ip g4 eco xtr fieldbus coupler ethernet/ip; generation 4; eco; extreme for wago-i/o-system 750
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Table 59: Blink code- table for the I/O LED signaling, error code 1
Error code 1: "Hardware and configuration error"
Error
Argument
9
10 ... 13
14
15
16

Table 60: Blink Code Table for the I/O LED Signaling, Error Code 2

Error Code 2: „Process image exceeded"
Error
Argument
1
2
3
Error Description
Solution
1. Turn off the power supply of the node.
Head station
2. Replace the head station.
initialization error
3. Turn on again the power supply of the node.
not used
1. Turn off the power supply of the node.
Maximum number of
2. Reduce the number of corresponding modules to a valid
gateway or mailbox
modules exceeded
3. Turn on again the power supply of the node.
Firmware loader was
1. Execute the last firmware update again.
loaded from backup.
2. If the error persists, contact I/O support.
Firmware was loaded
1. Execute the last firmware update again.
from backup.
2. If the error persists, contact I/O support.
Error Description
Solution
Not used
Maximum process
1. Turn off the power supply of the node.
image size
2. Reduce number of I/O modules.
exceeded
3. Turn on again the power supply of the node.
1. Turn off the power supply of the node.
Process image
2. Remove unsupported I/O modules.
generation error
3. Turn on again the power supply of the node.
number.
-
Diagnostics 141