Table 115: Coupler/Controller Configuration - WAGO 750-363/0040-0000 Manual

Fc ethernet/ip g4 eco xtr fieldbus coupler ethernet/ip; generation 4; eco; extreme for wago-i/o-system 750
Table of Contents

Advertisement

186 Fieldbus Communication
Instance 1

Table 115: Coupler/Controller configuration (64

Attribute ID
5
6
7
8
9
10
11
12..26
40..43
45
46
47
Manual
Version 1.0.0
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Acces
NV Name
s
Get
V
ProcessStat
e
Get
V
DNS_i_
Trmnldia
Get
V
CnfLen.
AnalogOut
Get
V
CnfLen.
AnalogInp
Get
V
CnfLen.
DigitalOut
Get
V
CnfLen.
DigitalInp
Set
NV Bk_Fault_
Reaction
Reserved for compatibility to DeviceNet
Reserved for compatibility to DeviceNet
Get
V
Bk_Led_Err
_Code
Get
V
Bk_Led_Err
_Arg
Get
V
Bk_Cfg_Dia
g_
Value
WAGO-I/O-SYSTEM 750
) – Instance 1
hex
Data type Description
USINT
State of coupler/controller, error
mask:
Bit 0: Local bus error
Bit 3: Module diagnostics (0x08)
Bit 7: Fieldbus error (0x80)
UINT
Module diagnostics:
Bit 0..7:
Module number
Bit 8..14: Module channel
Bit 15:
0/1 Error, repair/arisen
UINT
Number of I/O bits for the analog
output
UINT
Number of I/O bits for the analog
input
UINT
Number of I/O bits for the digital
output
UINT
Number of I/O bits for the digital
input
USINT
Fieldbus error reaction
0: stop local I/O cycles
1: set all output to 0
2: no error reaction
3: no error reaction
4: PFC task takes over control of
the outputs (apply to controllers)
UINT
I/O LED error code
UINT
I/O LED error argument
UINT
I/O-Module diagnostics
(Module specific diagnostic
state)
Note: This attribute has to be
read out before attribute 6
(DNS_i_Trmnldia), because
during the reading of attribute 6
the diagnostic byte contains
the data of the next diagnostic
Default
value
0
0
-
-
-
-
1
0
0
0