Device Description
Table 36: EMC – Emission of Interference
Standard
Conducted Emission of Interference – Line Connection DC Voltage
• EN 61000-6-3
• EN 60255-26
• EN 55032 Class A
*)
QP = Quasi Peak Detector; AV = Average Detector
**)
If necessary, please find different data in the section "Approval" (regarding approval for
EMC A or EMC B).

Table 37: Standards and Rated Conditions for Rail Applications (EN 50155)

4.1 Rated Operating Conditions
4.1.1 Altitude above sea level
4.1.2 Ambient operating temperature
4.1.3 Shock and vibration
4.1.4 Relative humidity
5.1 Power Supply
5.1.1.1 Master voltage fluctuations
5.1.1.2 Power interruptions
5.4 Surge, ESD, Burst Tests
5.5 EMC (Emission of Interference,
Immunity to Interference)
9.11 Materials (Fire Protection)
WAGO is a company certified in accordance with the IRIS quality standard.
Manual
Version 1.0.0
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Test Value
79 dB(µV) QP, 0.15 MHz ... 0.5 MHz
66 dB(µV) AV, 0.15 MHz ... 0.5 MHz
73 dB(µV) QP, 0.5 MHz ... 30 MHz
60 dB(µV) AV, 0.5 MHz ... 30 MHz
Minimum voltage
Maximum voltage
WAGO-I/O-SYSTEM 750
*)
Class / Standard Compliance
AX (EN 50125-1)
TX
1A and 1B (EN 61373)
95 % (coated PCBs)
0.725 × U
n
1.3 × U
n
S1
EN 50121-3-2
EN 50121-3-2
EN 50121-4
EN 50121-5
EN 45545-2
Hazard level HL3