Testing The Function Of The Fieldbus Node - WAGO 750-363/0040-0000 Manual

Fc ethernet/ip g4 eco xtr fieldbus coupler ethernet/ip; generation 4; eco; extreme for wago-i/o-system 750
Table of Contents

Advertisement

106 Commissioning
8.5

Testing the Function of the Fieldbus Node

1.
To ensure that the IP address is correct and to test communication with the
fieldbus node, first turn off the operating voltage of the fieldbus node.
2.
Create a non-serial connection between your PC and the fieldbus node.
The head station is initialized. The head station determines the I/O module
configuration of the fieldbus node and creates a process image.
During start-up, the I/O LED (red) flashes.
If the I/O LED lights up green after a brief period, the fieldbus node is operational.
If an error occurs during start-up indicated by the I/O LED flashing red, evaluate
the error code and argument and resolve the error.
More information about LED signaling
The exact description for evaluating the LED signal displayed is available in the
section "Diagnostics" > ... > "LED Signaling".
Manual
Version 1.0.0
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
WAGO-I/O-SYSTEM 750

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents