158 Fieldbus Communication
The addresses of the DNS server are configured via DHCP, BootP or web-based
management. Up to 2 DNS servers can be specified. The host identification can
be achieved with two functions; an internal host table is not supported.
11.1.2.5

SNTP-Client (Simple Network Time Protocol)

The SNTP client is used for synchronization of the time of day between a time
server (NTP and SNTP server Version 3 and 4 are supported) and the internal
system time in the (programmable) fieldbus coupler or controller. The protocol is
executed via a UDP port. Only unicast addressing is supported.
Configuration of the SNTP client
The configuration of the SNTP client is performed via the web-based
management system. The following parameters must be set:

Table 81: Meaning of the SNTP Parameters

Parameter
WBM page "TCP/IP"  "(S)NTP
Server"
WBM page "TCP/IP" 
„SNTP Update Time (sec,
max. 65535) "
WBM page "Clock" 
"Timezone (+/-
hour:minute)"
WBM page "Port"
"SNTP"
11.1.2.6

FTP-Server (File Transfer Protocol)

The file transfer protocol (FTP) enables files to be exchanged between different
network stations regardless of operating system.
In the case of the ETHERNET coupler/controller, FTP is used to store and read
the HTML pages created by the user, the IEC61131 program and the IEC61131
source code in the (programmable) fieldbus coupler or controller.
A total memory of 1 GB is available for the internal file system.
Cycles for flash limited to 1 million!
Up to 1 million write cycles per sector are allowed when writing the flash for the
file system. The file system supports "Wear-Leveling", so that the same sectors
are not always written to.
Manual
Version 1.0.0
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Meaning
The address assignment can be made over an IP address.
The update time indicates the interval in seconds, in which the
synchronization with the time server is to take place.
To operate the ETHERNET couplers/controllers with SNTP in
various countries, you must specify a time zone. The time zone
relative to GMT (Greenwich Mean time). A range of -12 to +14
hours is acceptable.
It indicates whether the SNTP Client is to be activated or
deactivated.