Page 2
We wish to point out that the software and hardware terms as well as the trademarks of companies used and/or mentioned in the present manual are generally protected by trademark or patent. WAGO is a registered trademark of WAGO Verwaltungsgesellschaft mbH. Manual Version 1.3.0...
WAGO-I/O-SYSTEM 750 XTR Table of Contents 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Table of Contents Notes about this Documentation ............. 5 Validity of this Documentation..............5 Copyright ....................5 Symbols ....................6 Number Notation ..................8 Font Conventions ................... 8 Important Notes ..................
Page 4
Table of Contents WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Configuration via WAGO-I/O-CHECK ........... 41 4.5.1 Toolbar on the Configuration Dialog ..........41 4.5.2 Navigation Bar ................. 42 4.5.2.1 “Settings” Page ................44 4.5.2.2 “Offset/Gain” Page............... 46 4.5.2.3...
(2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR). The I/O module 750-563/040-000 shall only be installed and operated according to the instructions in this manual, in the system description for the WAGO-I/O- SYSTEM 750 XTR and in the manual for the used fieldbus coupler/controller.
Notes about this Documentation WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Symbols Personal Injury! Indicates a high-risk, imminently hazardous situation which, if not avoided, will result in death or serious injury. Personal Injury Caused by Electric Current! Indicates a high-risk, imminently hazardous situation which, if not avoided, will result in death or serious injury.
Page 7
WAGO-I/O-SYSTEM 750 XTR Notes about this Documentation 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Additional Information: Refers to additional information which is not an integral part of this documentation (e.g., the Internet). Manual Version 1.3.0...
Notes about this Documentation WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Number Notation Table 1: Number Notation Number Code Example Note Decimal Normal notation Hexadecimal 0x64 C notation Binary '100' In quotation marks, nibble separated '0110.0100' with dots (.)
2.1.1 Subject to Changes WAGO Kontakttechnik GmbH & Co. KG reserves the right to provide for any alterations or modifications. WAGO Kontakttechnik GmbH & Co. KG owns all rights arising from the granting of patents or from the legal protection of utility patents.
These modules contain no parts that can be serviced or repaired by the user. The following actions will result in the exclusion of liability on the part of WAGO Kontakttechnik GmbH & Co. KG: •...
WAGO-I/O-SYSTEM 750 XTR Important Notes 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR • Observe national and local regulations for the disposal of electrical and electronic equipment. • Clear any data stored on the electrical and electronic equipment. • Remove any added battery or memory card in the electrical and electronic equipment.
Important Notes WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Safety Advice (Precautions) For installing and operating purposes of the relevant device to your system the following safety precautions shall be observed: Do not work on devices while energized! All power sources to the device shall be switched off prior to performing any installation, repair or maintenance work.
Page 13
Power from SELV/PELV power supply only! All field signals and field supplies connected to this XTR I/O module (750-563/040-000) must be powered from SELV/PELV power supply(s)! Do not touch hot surfaces! The surface of the housing can become hot during operation. If the device was operated at high ambient temperatures, allow it to cool off before touching it.
Page 14
Important Notes WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Do not reverse the polarity of connection lines! Avoid reverse polarity of data and power supply lines, as this may damage the devices involved. Avoid electrostatic discharge! The devices are equipped with electronic components that may be destroyed by electrostatic discharge when touched.
WAGO-I/O-SYSTEM 750 XTR Device Description 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Device Description The I/O module 750-563/040-000 (2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR) generates ... • Adjustable output currents in the range of 0/4 mA … 20 mA •...
Page 16
Device Description WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Do not exceed maximum values via power contacts! The maximum current that can flow through the power jumper contacts is 10 A. The power jumper contacts can be damaged and the permissible operating temperature can be exceeded by higher current values.
Device Description WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Connectors 3.2.1 Data Contacts/Local Bus Communication between the fieldbus coupler/controller and the I/O modules as well as the system supply of the I/O modules is carried out via the local bus. The contacting for the local bus consists of 6 data contacts, which are available as self-cleaning gold spring contacts.
The blade contacts are sharp-edged. Handle the I/O module carefully to prevent injury. Do not touch the blade contacts. The I/O module 750-563/040-000 has 2 self-cleaning power jumper contacts that supply and transmit power for the field side. The contacts on the left side of the I/O module are designed as blade contacts and those on the right side as spring contacts.
I/O module can be achieved even in the presence of interference acting on the signal cable. For further information about shielding, see system manual WAGO-I/O-SYSTEM 750 XTR, section “Connect Devices” > … > “Shielding.”...
State Function Local bus timeout Green Local bus OK No group error ERROR Group error Local bus timeout Green Local bus OK No group error ERROR Group error Operating Elements The I/O module 750-563/040-000 has no operating elements. Manual Version 1.3.0...
Device Description WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR 3.6.4 Outputs Table 10: Technical Data – Outputs No. of outputs Connection type 2- or 4-wire technology Output voltage (configurable) Minimum voltage 20.4 V (24 V - 15%) 6 V …...
The following approvals have been granted to 750-563/040-000 I/O modules: Conformity Marking UL508 Korea Certification MSIP-REM-W43-AOM750 The following Ex approvals have been granted to 750-563/040-000 I/O modules: ANSI/ISA 12.12.01 Class I, Div2 ABCD T4 TÜV 17 ATEX 193969 X II 3 G Ex ec IIC T4 Gc IECEx TUN 16.0046X...
Device Description WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Table 17: Climatic and Mechanical Environmental Conditions and Shipbuilding Standard Test Value Transport EN 60870-2-2 Ct2(2k4) (except precipitation/water/moisture) Mechanical Environmental Conditions EN 61850-3 Achieved EN 60870-2-2 EN 60721-3-1...
WAGO-I/O-SYSTEM 750 XTR Device Description 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR The I/O module 750-563/040-000 meets the following EMC standards as these standards relate to the I/O module: Table 18: EMC – Immunity to Interference Standard Test Value Electrostatic Discharge •...
Page 30
Device Description WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Table 18: EMC – Immunity to Interference Standard Test Value Line Frequency Disturbances • EN 60255-26 Standard not applicable Alternating Components of the Voltage to DC Line Connections •...
EN 50121-3-2 5.5 EMC (Emission of Interference, EN 50121-3-2 Immunity to Interference) EN 50121-4 EN 50121-5 9.11 Materials (Fire Protection) EN 45545-2 Hazard level HL3 WAGO is a company certified in accordance with the IRIS quality standard. Manual Version 1.3.0...
750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Process Image Overview The analog output module 750-563/040-000 (2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR) provides 16 bits of data and optional (with PROFIBUS/PROFINET) 8 status bits per channel. The digitalized output value is output in a data word (16 bit) via the process image of the fieldbus coupler/controller as output byte 0 (low) and output byte 1 (high).
Process Image WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Table 24: Status Byte S0 Status Byte S0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Reg_Com ERR_1 ERR24V TEMP_1...
WAGO-I/O-SYSTEM 750 XTR Process Image 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Table 25: Control Byte C1 Control Byte C1 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Reg_Com Reg_Com Process Data Communication...
Process Image WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Process Values Table 27: Process Values, 0 mA … 20 mA Data Format 0 ... 65535 Manufacturer calibration, without user scaling Numeric value 0 mA ... 20 mA, [I...
WAGO-I/O-SYSTEM 750 XTR Process Image 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Table 30: Number Formats Number Formats 0 mA 20 mA View 4 mA 20 mA 18 V 0x0000 0x7FFF 0x8000 0xFFFF 0 … 65535 32767 32768...
Process Image WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Function Description The conversion algorithm takes into account all calculation and assessment steps of the process data to the analog output value. The individual steps are explained in this section. The following flowchart provides an overview of the stepwise processing of the input value.
WAGO-I/O-SYSTEM 750 XTR Process Image 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR 4.4.2 Step 2 – Y User Scaling The value for Y is generated with the user scaling. The X value serves as the input value for the user scaling. With user scaling switched off, the X...
Process Image WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR 4.4.4 Step 4 – Y Limit Control The limit control monitors whether the Y value is in DAC format in the required value range. This value range is defined by the parameter underrange limiting value (UNR) and the overrange limiting value (OVR).
Process Image 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Configuration via WAGO-I/O-CHECK Figure 8: Example: Parameterization Dialog of I/O Module 750-563/040-000 The parameterization dialog is divided into the following areas: • Title bar with position and item number of the selected I/O module •...
Process Image WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Table 33: Toolbar Button Function Description Exit Closes the configuration dialog. Opens an existing parameterization file. WAGO- Open I/O-CHECK displays the default dialog for opening files. Saves the current parameter in a parameter file.
WAGO-I/O-SYSTEM 750 XTR Process Image 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Figure 10: Navigation Between Channels You can choose between the following menu items: Table 34: Overview of the Navigation Bar Menu Items Menu Item Marking [Channel 1] opens a tree structure with settings, offset/gain and process data for channel 1.
Process Image WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR values to the I/O module, click [Write]. The change icon goes away, the [Write] button is grayed out again. The Process Data page displays information about the process value of the I/O module and displays status messages.
WAGO-I/O-SYSTEM 750 XTR Process Image 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Table 35: Modifiable Parameters of the “Settings” Page Description Input/Selection Description Operating mode 0 mA … 20 mA Selection of the operating mode of the I/O module 4 mA … 20 mA (0)6 V …...
Process Image WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Values must be input in raw data format! The values for the lower and upper limiting value must be entered in raw data format, i.e., if a user scaling is set, it must be taken into account for the entry of the limiting values.
WAGO-I/O-SYSTEM 750 XTR Process Image 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Table 36: Modifiable Parameters of the “Offset/Gain” Page Description Input/Selection Description User scaling Activation of the user scaling Offset … +65535 Setting of the offset of the user scaling Gain 0 …...
Process Image WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR 4.5.2.3 “Process Data” Page Figure 13: “Process Data” Page Information about the process data of the I/O module is displayed on the Process Data page, e.g., output stage errors, supply or limiting value exceeded.
750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Mounting Mounting Sequence Fieldbus couplers, controllers and I/O modules of the WAGO-I/O-SYSTEM 750 are snapped directly on a carrier rail in accordance with the European standard EN 60175 (DIN 35). The reliable positioning and connection is made using a tongue and groove system.
WAGO-I/O-SYSTEM 750 XTR Mounting 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Inserting and Removing Devices Do not touch hot surfaces! The surface of the housing can become hot during operation. If the device was operated at high ambient temperatures, allow it to cool off before touching it.
Mounting WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Press the I/O module into the assembly until the I/O module snaps into the carrier rail. Figure 15: Snap the I/O Module into Place (Example) With the I/O module snapped in place, the electrical connections for the data contacts and power jumper contacts (if any) to the fieldbus coupler/controller or to the previous or possibly subsequent I/O module are established.
WAGO-I/O-SYSTEM 750 XTR Mounting 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Figure 16: Removing the I/O Module (Example) Electrical connections for data or power jumper contacts are disconnected when removing the I/O module. Manual Version 1.3.0...
Only one conductor may be connected to each CAGE CLAMP Do not connect more than one conductor at one single connection! If more than one conductor must be routed to one connection, these must be connected in an up-circuit wiring assembly, for example using WAGO feed- through terminals. ®...
I/O module can be achieved even in the presence of interference acting on the signal cable. For further information about shielding, see system manual WAGO-I/O-SYSTEM 750 XTR, section “Connect Devices” > … > “Shielding.”...
WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Use in Hazardous Environments The WAGO-I/O-SYSTEM 750 (electrical equipment) is designed for use in Zone 2 hazardous areas and shall be used in accordance with the marking and installation regulations.
WAGO-I/O-SYSTEM 750 XTR Use in Hazardous Environments 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Marking Configuration Examples 7.1.1 Marking for Europe According to ATEX and IECEx Figure 20: Marking Example According to ATEX and IECEx Figure 21: Text Detail – Marking Example According to ATEX and IECEx Manual Version 1.3.0...
Use in Hazardous Environments WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Table 39: Description of Marking Example According to ATEX and IECEx Marking Description TUEV 07 ATEX 554086 X Approving authority resp. certificate numbers IECEx TUN 09.0001 X...
WAGO-I/O-SYSTEM 750 XTR Use in Hazardous Environments 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Figure 22: Marking Example for Approved Ex i I/O Module According to ATEX and IECEx Figure 23: Text Detail – Marking Example for Approved Ex i I/O Module According to ATEX and...
Use in Hazardous Environments WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Table 40: Description of Marking Example for Approved Ex i I/O Module According to ATEX and IECEx Marking Description TUEV 12 ATEX 106032 X Approving authority resp. certificate numbers...
WAGO-I/O-SYSTEM 750 XTR Use in Hazardous Environments 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR 7.1.2 Marking for the United States of America (NEC) and Canada (CEC) Figure 24: Marking Example According to NEC Figure 25: Text Detail – Marking Example According to NEC 500...
Use in Hazardous Environments WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Figure 26: Text Detail – Marking Example for Approved Ex i I/O Module According to NEC 505 Table 42: Description of Marking Example for Approved Ex i I/O Module According to NEC 505...
WAGO-I/O-SYSTEM 750 XTR Use in Hazardous Environments 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Figure 28: Text Detail – Marking Example for Approved Ex i I/O Modules According to CEC 18 attachment J Table 44: Description of Marking Example for Approved Ex i I/O Modules According to CEC 18...
Use in Hazardous Environments WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Installation Regulations For the installation and operation of electrical equipment in hazardous areas, the valid national and international rules and regulations which are applicable at the installation location must be carefully followed.
Page 65
WAGO-I/O-SYSTEM 750 XTR Use in Hazardous Environments 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Explosive atmosphere occurring simultaneously with assembly, installation or repair work must be ruled out. Among other things, these include the following activities • Insertion and removal of components •...
Use in Hazardous Environments WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR 7.2.2 Special Notes Regarding ANSI/ISA Ex For ANSI/ISA Ex acc. to UL File E198726, the following additional requirements apply: • Use in Class I, Division 2, Group A, B, C, D or non-hazardous areas only •...
List of Tables WAGO-I/O-SYSTEM 750 XTR 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR List of Tables Table 1: Number Notation ................... 8 Table 2: Font Conventions .................. 8 Table 3: Legend for Figure “View” ..............17 Table 4: Legend for Figure “Power Jumper Contacts” ........19 ®...
Page 69
WAGO-I/O-SYSTEM 750 XTR List of Tables 750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR Table 43: Description of Marking Example for Approved Ex i I/O Modules According to NEC 506 ................62 Table 44: Description of Marking Example for Approved Ex i I/O Modules According to CEC 18 attachment J ............63...
Page 70
WAGO Kontakttechnik GmbH & Co. KG Postfach 2880 • D - 32385 Minden Hansastraße 27 • D - 32423 Minden Phone: +49 571 887 – 0 Fax: +49 571 887 – 844169 E-Mail: info@wago.com Internet: www.wago.com...
Need help?
Do you have a question about the 750-563/040-000 and is the answer not in the manual?
Questions and answers