Apply Ip Address Permanently (Option "Static") - WAGO 750-363/0040-0000 Manual

Fc ethernet/ip g4 eco xtr fieldbus coupler ethernet/ip; generation 4; eco; extreme for wago-i/o-system 750
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
8.4

Apply IP address permanently (option "static")

For permanent address assignment, the IP stored in the EEPROM must be
used!
To apply permanently the new IP address assigned via DHCP or BootP in the
fieldbus coupler/controller, the assigned or desired settings for IP address,
subnet mask and default gateway must be entered on the WBM "TCP/IP" page.
In addition the option "IP configuration source: static" must be activated.
Then, the IP address is stored in the EEPROM and used as static address.
You can enable the option "IP configuration source: static" in the Web-based
Management System.
1.
Open the WBM (see chapter: "Configuring in the Web-Based Management
System (WBM)" >> "Open WBM").
2.
Select the WBM page "TCP/IP".
3.
Enter the assigned or desired settings for IP address, subnet mask and
default gateway in the fields "IP address", "Subnet mask" and "Default
gateway".
4.
Enable the option "IP configuration source: "static".
At the same time, the use of the DHCP/BootP server is diabled.
Confirm your changes with button [SUBMIT].
5.
6.
Select the "Administration" WBM page.
Click on the button [Software Reset] at the bottom of the page in order for
7.
the settings to take effect.
Alternatively restart the fieldbus node.
Then the fieldbus node starts with the configurations and the assigned IP
address, which were previously loaded into the EEPROM. The connection
to the browser is interrupted.
8.
Now you must use the new IP address, if you want to access again on the
WBM of this fieldbus node via browser.
Commissioning 105