WAGO-I/O-SYSTEM 750
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR

Figure 8: Field supply (sensor/actuator) (example)

Table 7: Legend for the "Field supply (sensor/actuator)" figure

Position Beschreibung
1
2
3
In exceptional instances, I/O modules can be directly connected to the
field supply!
The 24 V field supply can be connected also directly to a bus module, if the
connection points are not needed for the peripheral device supply. In this case,
the connection points need the connection to the power jumper contacts.
The field-side power supply is automatically derived from the power jumper
contacts when snapping an I/O module.
The current load of the power contacts must not exceed 10 A on a continual
basis.
By inserting an additional power supply module, the field supply via the power
contacts is disrupted. From there a new power supply occurs which may also
contain a new voltage potential.
3.4.4.2

Fusing via Power Supply Module

Internal fusing of the field supply is possible for various field voltages via an
appropriate power supply module.
Field supply 24 VDC
Field supply 0 V
Power jumper contacts (potential distribution to adjacent I/O modules)