WAGO 750-363/0040-0000 Manual page 131

Fc ethernet/ip g4 eco xtr fieldbus coupler ethernet/ip; generation 4; eco; extreme for wago-i/o-system 750
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 Configuring via the Web-Based Management System (WBM) 131
750-363/0040-0000 FC EtherNet/IP G4 ECO XTR
Tabelle 53: WBM-Seite „TCP/IP"
Network Settings (non-volatile)
Eintrag
IP configuration
source
IP address conflict
detection (ACD)
IP address
Subnet mask
Default gateway
Host name
Domain name
DNS server 1
DNS server 2
DIP switch base IP
address
IP Fragment TTL [s]
(max.255)
Standardwert Wert (Beispiel)
BootP
DHCP
static
0.0.0.0
192.168.1.180
255.255.255.0 255.255.255.0
0.0.0.0
0.0.0.0
0030DEXXXX
0030DE000000
XX
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
192.168.1
192.168.5
60
60
Beschreibung
Activate "Bootstrap Protocol".
Deactivate "Bootstrap Protocol".
Activate "Dynamic Host
Configuration Protocol".
Deactivate "Dynamic Host
Configuration Protocol"
Use IP address from EEPROM.
Do not use IP address from
EEPROM.
Activate IP address conflict detection
acc. to RFC5227.
Deactivate IP address conflict
detection acc. to RFC5227
(an IP address conflict is detected
once during initialization).
Enter IP address.
Enter subnet mask.
Enter gateway.
Enter host name.
Enter domain name.
Enter IP address of the first DNS server.
Enter optional IP address of the second
DNS server.
Network address for the configuration of
the IP address with DIP switch.
Life of a packet (Time to Live).
Version 1.0.0
Manual

Hide quick links:

Advertisement

Table of Contents
loading