Parameter Description
DN-31 Store Data Values
Option:
Function:
Parameter values changed via DeviceNet are not
automatically stored in non-volatile memory. Use
this parameter to activate a function that stores
parameter values in the EEPROM non-volatile
memory, so changed parameter values are
retained at power-down.
[0]
Off
Deactivates the non-volatile storage function.
*
[1]
Store edit
Stores all parameter values from the active set-
setup
up in the non-volatile memory. The selection
returns to [0] Off when all values have been
stored.
[2]
Store all
Stores all parameter values for all set-ups in the
setups
non-volatile memory. The selection returns to [0]
Off when all parameter values have been stored.
DN-32 Devicenet Revision
Range:
Function:
0
[0 - 65535] View the DeviceNet revision number. This
*
parameter is used for EDS file creation.
DN-33 Store Always
Option: Function:
[0]
Off Deactivates non-volatile storage of data.
*
[1]
On
Stores parameter data received via DeviceNet MCA 104
in EEPROM non-volatile memory as default.
DN-34 DeviceNet Product Code
Range:
120
[0 - 65535]
*
DN-39 Devicenet F Parameters
Array [1000].
No keypad access.
Range:
Function:
0
[0 - 0] This parameter is used to configure the frequency
*
converter via DeviceNet MCA 104 and build the
EDS file.