Parameter Description
LC-02 Stop Event
Option:
[71]
Logic Controller
Time-out 4
[72]
Logic Controller
3
3
Time-out 5
[73]
Logic Controller
Time-out 6
[74]
Logic Controller
Time-out 7
[76]
Digital Input x30
2
[77]
Digital Input x30
3
[78]
Digital Input x30
4
[80]
No Flow
[81]
Dry Pump
[82]
End of Curve
[83]
Broken Belt
[90]
ECB Drive Mode
[91]
ECB Bypass Mode
[92]
ECB Test Mode
[100] Fire Mode
[140] ATEX ETR cur.
warning
[141] ATEX ETR cur.
alarm
[142] ATEX ETR freq.
warning
[143] ATEX ETR freq.
alarm
LC-03 Reset Logic Controller
Option:
[0]
Do not reset Logic
*
Controller
[1]
Reset Logic
Controller
3.25.3 Comparators
Comparators are used for comparing continuous variables
(that is output frequency, output current, analog input, and
so on.) to fixed preset values.
186
Function:
Use the result of timer 4 in the logic
rule.
Use the result of timer 5 in the logic
rule.
Use the result of timer 6 in the logic
rule.
Use the result of timer 7 in the logic
rule.
See parameter LC-15 RS-FF Operand S,
parameter LC-16 RS-FF Operand R.
Function:
Retains programmed settings in
parameter group LC-## Logic
Controller.
Resets all parameters in parameter
group LC-## Logic Controller to default
settings.
03/2016 All rights reserved.
Illustration 3.75 Comparators
There are digital values that are compared to fixed time
values. See explanation in parameter LC-10 Comparator
Operand. Comparators are evaluated once in each scan
interval. Use the result (true or false) directly. All
parameters in this parameter group are array parameters
with index 0–5. Select index 0 to program comparator 0,
select index 1 to program comparator 1, and so on.
LC-10 Comparator Operand
Array [6]
Option:
[0]
DISABLED
*
[1]
Reference %
[2]
Feedback %
[3]
Motor speed
[4]
Motor Current
[5]
Motor torque
[6]
Motor power
[7]
Motor Rated Voltage
[8]
DC-link voltage
[9]
Motor Thermal
[10]
Drive thermal
[11]
Heat sink temp.
[12]
Analog input AI53
[13]
Analog input AI54
[14]
Analog input AIFB10
[15]
Analog input AIS24V
[17]
Analog input AICCT
[18]
Pulse input FI29
[19]
Pulse input FI33
[20]
Alarm number
[21]
Warning number
[22]
Analog input x30 11
[23]
Analog input x30 12
[29]
Number Of Pump Running
[30]
Counter A
[31]
Counter B
[40]
Analog input x42/1
[41]
Analog input x42/3
[42]
Analog input x42/5
[50]
FALSE
[51]
TRUE
Function:
Select the variable to be
monitored by the
comparator.