How to Program
2.1.13 Restore to Default Settings
Restore the frequency converter to default settings in 2
ways.
Recommended restore (via parameter H-03 Restore
Factory Settings)
1.
Select parameter H-03 Restore Factory Settings.
2.
Press [OK].
3.
Select restore.
4.
Press [OK].
5.
Cut off the mains supply and wait until the
display turns off.
6.
Reconnect the mains supply - the frequency
converter is now reset.
7.
Change parameter H-03 Restore Factory Settings
back to [0] Normal Operation.
NOTICE
Resets parameters selected in Quick Start menu with
default factory setting.
Parameter H-03 Restore Factory Settings restores all
except:
Parameter SP-50 RFI Filter.
Parameter O-30 Protocol.
Parameter O-31 Address.
Parameter O-32 Drive Port Baud Rate.
Parameter O-35 Minimum Response Delay.
Parameter O-36 Maximum Response Delay.
Parameter O-37 Maximum Inter-Char Delay.
Parameter ID-00 Operating hours to
parameter ID-05 Over Volt's.
Parameter ID-20 Historic Log: Event to
parameter ID-22 Historic Log: Time.
Parameter ID-30 Alarm Log: Error Code to
parameter ID-32 Alarm Log: Time.
Manual restore
1.
Disconnect from mains and wait until the display
turns off.
2.
Press [Status] - [Main Menu] - [OK] at the same
time while power up for keypad, Graphical
Display
3.
Release the keys after 5 seconds
4.
The frequency converter is now programmed
according to default settings.
DET-620D
AF-600 FP™ Programming Guide
This procedure initializes all except:
•
•
•
•
NOTICE
Manual restore:
•
•
•
NOTICE
After restore and power cycling, the display does not
show any information until after a couple of minutes.
03/2016 All rights reserved.
Parameter ID-00 Operating hours.
Parameter ID-03 Power Up's.
Parameter ID-04 Over Temp's.
Parameter ID-05 Over Volt's.
Resets serial communication.
Resets parameter SP-50 RFI Filter and fault log
settings.