GE Ecomagination AF-600 FP Programming Manual page 62

Fan & pump drive
Table of Contents

Advertisement

Parameter Description
P-44 d-axis Inductance Sat. (LdSat)
Range:
Function:
0.0 mH
[0 - 1000
Enter the inductance saturation of Ld.
*
mH]
Ideally, this parameter has the same value
as parameter P-37 d-axis Inductance (Ld). If
the motor supplier provides an induction
curve, enter the induction value at 200% of
the nominal value.
P-45 q-axis Inductance Sat. (LqSat)
Range:
Function:
0.0 mH
[0 - 1000
This parameter corresponds to the
*
mH]
inductance saturation of Lq. Ideally, this
parameter has the same value as
parameter P-38 q-axis Inductance (Lq). If the
motor supplier provides an induction curve,
enter the induction value at 200% of the
nominal value.
P-46 Position Detection Gain
Range:
Function:
100 %
[20 -
Adjusts the amplitude of the test pulse
*
200 %]
during position detection at start. Adjust
this parameter to improve the position
measurement.
P-47 Torque Calibration
Option:
[0]
Off
*
[1]
1st start after pwr-up
[2]
Every start
[3]
1st start with store
[4]
Every start with store
P-48 Inductance Sat. Point
Range:
Function:
35 %
[1 - 500 %]
Enter the induction saturation point.
*
P-62 Locked Rotor Protection
Option:
[0]
Off
*
[1]
On
P-63 Locked Rotor Detection Time [s]
Range:
0.10 s
[0.05 - 1 s]
*
DET-620D
AF-600 FP™ Programming Guide
Function:
Function:
Function:
03/2016 All rights reserved.