Parameter Description
O-05 End-of-Timeout Function
Option:
3
3
[0]
Hold set-
up
[1]
Resume
*
set-up
O-06 Reset Control Word Timeout
Option:
[0]
Do not
*
reset
[1]
Do
reset
O-07 Diagnosis Trigger
Option:
[0]
Disable
*
[1]
Trigger on
alarms
[2]
Trigger
alarm/warn.
82
Function:
Select the action after receiving a valid control
word following a timeout.
This parameter is active only when
parameter O-04 Control Word Timeout Function is
set to:
[7] Set-up 1.
[8] Set-up 2.
[9] Set-up 3.
[10] Set-up 4.
Retains the set-up selected in
parameter O-04 Control Word Timeout Function
and shows a warning until parameter O-06 Reset
Control Word Timeout toggles. Then the
frequency converter resumes its original set-up.
Resumes the set-up that was active before the
timeout.
Function:
This parameter is active only when option [0] Hold
set-up has been selected in parameter O-05 End-of-
Timeout Function.
Retains the set-up specified in
parameter O-04 Control Word Timeout Function:
[7] Set-up 1.
[8] Set-up 2.
[9] Set-up 3.
[10] Set-up 4.
Returns the drive to the original set-up following a
control word timeout. When the value is set to [1]
Do reset, the drive performs the reset and
immediately reverts to the [0] Do not reset setting.
Function:
To send no extended diagnosis data (EDD),
select [0] Disable. To send EDD upon alarms,.
select [1] Trigger on alarms. To send EDD
upon alarms or warnings, select [2] Trigger
alarm/warn. Not all fieldbusses support the
diagnosis functions.
O-08 Readout Filtering
If the speed feedback value readouts on fieldbus are fluctuating,
this function is used. Select filtered, if the function is required. A
power cycle is required for changes to take effect.
Option:
[0]
Motor Data
*
Std-Filt.
[1]
Motor Data
LP-Filter
O-09 Communication Charset
Option:
[0]
[1]
*
[2]
3.9.2 O-1# Control Settings
O-10 Control Word Profile
Option:
[0]
Drive Profile
*
[1]
PROFIdrive
profile
[5]
ODVA
O-13 Configurable Status Word STW
Array [16]
Option:
[0]
No function
[1]
Profile Default The function corresponds to the profile
*
[2]
Alarm 68 Only Only set if alarm 68, Safe stop occurs.
03/2016 All rights reserved.
Function:
Normal fieldbus readouts.
Filtered fieldbus readouts of the following
parameters:
Parameter DR-10 Power [kW].
Parameter DR-11 Power [hp].
Parameter DR-12 Motor Voltage.
Parameter DR-14 Motor current.
Parameter DR-16 Torque [Nm].
Parameter DR-17 Speed [RPM].
Parameter DR-22 Torque [%].
Parameter DR-25 Torque [Nm] High.
Function:
ISO 8859-1
ANSI X3.4
UTF - 8
Function:
Select the interpretation of the control and
status words corresponding to the installed
network. Only the selections valid for the
network installed in slot A are visible in the
LPC display.
Available only with DeviceNet MCA 104
and EtherNet IP .
Function:
This parameter enables configuration of
bits 12–15 in the status word.
default selected in parameter O-10 Control
Word Profile.
DET-620D