Parameter Description
T-80 Power Reference Factor
Range:
Function:
100 %
[0 -
Set the percentage of the rated motor size (set
100 %]
in parameter P-07 Motor Power [kW] or
*
parameter P-02 Motor Power [HP]), which shows
the average power yielded at the time running
with fixed speed (before upgrade with variable
speed control).
Set a value different from 0 to start counting.
T-81 Energy Cost
Range:
Function:
1
[0 - 999999.99] Set the actual cost for a kWh in local
*
currency. If the energy cost is changed later
on, it impacts the calculation for the entire
period.
T-82 Investment
Range:
Function:
0
[0 -
Set the value of the investment spent on
*
999999999]
upgrading the plant with speed control, in
same currency as used in
parameter T-81 Energy Cost.
T-83 Energy Savings
Range:
Function:
0 kWh
[0 - 0
This parameter allows a readout of the
*
kWh]
accumulated difference between the reference
power and the actual output power.
If motor size is set in hp
(parameter P-02 Motor Power [HP]), the
equivalent kW value is used for the energy
savings.
T-84 Cost Savings
Range:
Function:
0
[0 - 2147483647] This parameter allows a readout of the
*
calculation based on the above equation
(in local currency).