GE Ecomagination AF-600 FP Programming Manual page 193

Fan & pump drive
Table of Contents

Advertisement

Parameter Description
LC-52 Logic Controller Action
Array [20]
Option:
[4]
Select set-up 3
3
3
[5]
Select set-up 4
[10]
Select preset ref
0
[11]
Select preset ref
1
[12]
Select preset ref
2
[13]
Select preset ref
3
[14]
Select preset ref
4
[15]
Select preset ref
5
[16]
Select preset ref
6
[17]
Select preset ref
7
[18]
Select Accel/
Decel 1
[19]
Select Accel/
Decel 2
[22]
Run
[23]
Run reverse
[24]
Stop
[26]
DC Brake
[27]
Coast
[28]
Freeze output
[29]
Start timer 0
[30]
Start timer 1
192
Function:
Changes the active set-up
(parameter K-10 Active Set-up) to 3.
Changes the active set-up
(parameter K-10 Active Set-up) to 4. If the
set-up is changed, it merges with other
set-up commands coming from either
the digital inputs or via a fieldbus.
Selects preset reference 0.
Selects preset reference 1.
Selects preset reference 2.
Selects preset reference 3.
Selects preset reference 4.
Selects preset reference 5.
Selects preset reference 6.
Selects preset reference 7. If the active
preset reference is changed, it merges
with other preset reference commands
coming from either the digital inputs or
via a fieldbus.
Selects ramp 1.
Selects ramp 2.
Issues a start command to the frequency
converter.
Issues a start reverse command to the
frequency converter.
Issues a stop command to the frequency
converter.
Issues a DC stop command to the
frequency converter.
The frequency converter coasts
immediately. All stop commands
including the coast command stop the
LC.
Freezes the output frequency of the
frequency converter.
Starts timer 0, see parameter LC-20 Logic
Controller Timer for further description.
Starts timer 1, see parameter LC-20 Logic
Controller Timer for further description.
03/2016 All rights reserved.
LC-52 Logic Controller Action
Array [20]
Option:
Function:
[31]
Start timer 2
Starts timer 2, see parameter LC-20 Logic
Controller Timer for further description.
[32]
Set digital out
Any output with digital output 1 selected
A low
is low (off).
[33]
Set digital out B
Any output with digital output 2 selected
low
is low (off).
[34]
Set digital out
Any output with digital output 3 selected
C low
is low (off).
[35]
Set digital out
Any output with digital output 4 selected
D low
is low (off).
[36]
Set digital out E
Any output with digital output 5 selected
low
is low (off).
[37]
Set digital out F
Any output with digital output 6 selected
low
is low (off).
[38]
Set digital out
Any output with digital output 1 selected
A high
is high (closed).
[39]
Set digital out B
Any output with digital output 2 selected
high
is high (closed).
[40]
Set digital out
Any output with digital output 3 selected
C high
is high (closed).
[41]
Set digital out
Any output with digital output 4 selected
D high
is high (closed).
[42]
Set digital out E
Any output with digital output 5 selected
high
is high (closed).
[43]
Set digital out F
Any output with digital output 6 selected
high
is high (closed).
[60]
Reset Counter A Resets counter A to 0.
[61]
Reset Counter B Resets counter B to 0.
[62]
Counter A (up)
[63]
Counter A
(down)
[64]
Counter B (up)
[65]
Counter B
(down)
[70]
Start Timer 3
Starts timer 3, see parameter LC-20 Logic
Controller Timer for further description.
[71]
Start Timer 4
Starts timer 4, see parameter LC-20 Logic
Controller Timer for further description.
[72]
Start Timer 5
Starts timer 5, see parameter LC-20 Logic
Controller Timer for further description.
[73]
Start Timer 6
Starts timer 6, see parameter LC-20 Logic
Controller Timer for further description.
[74]
Start Timer 7
Starts timer 7, see parameter LC-20 Logic
Controller Timer for further description.
[80]
Sleep Mode
Starts the sleep mode.
DET-620D