Parameter Description
3.18 LG-## Logs & I/O Opt. Status
3.18.1 LG-0# Maintenance Log
This group contains the last 10 preventive maintenance
events. Maintenance log 0 is the latest and maintenance
3
3
log 9 the oldest.
By selecting 1 of the logs and pressing [OK], the
maintenance item, action, and time of the occurrence are
shown in parameter LG-00 Maintenance Log: Item –
parameter LG-03 Maintenance Log: Date and Time.
The alarm log key allows access to both alarm log and
maintenance log.
LG-00 Maintenance Log: Item
Array [10]
For details about a fault code, refer to the design guide.
Range:
0
[0 - 255] Locate the meaning of the maintenance item in
*
LG-01 Maintenance Log: Action
Array [10]
For details about a fault code, refer to the design guide.
Range:
0
[0 - 255] Locate the meaning of the maintenance item in
*
LG-02 Maintenance Log: Time
Array [10]
Range:
0 s
[0 - 2147483647 s] Shows when the logged event
*
LG-03 Maintenance Log: Date and Time
Array [10]
Range:
0
[0 - 0] Shows when the logged event occurred.
*
NOTICE
This requires that the date and time is
programmed in parameter K-70 Date and
Time.
Date format depends on the setting in
parameter K-71 Date Format, while the time format
depends on the setting in parameter K-72 Time
Format.
122
Function:
the description of parameter T-10 Maintenance
Item.
Function:
the description of parameter T-11 Maintenance
Action.
Function:
occurred. Time is measured in s since
last power-up.
Function:
LG-03 Maintenance Log: Date and Time
Array [10]
Range:
NOTICE
When mounting a Analog I/O option card, a battery
back-up of date and time is included.
3.18.2 LG-1# Fire Mode Log
The log covers the latest 10 faults which have been
suppressed by the Fire mode function. See parameter
group FB-0#, Fire Mode. The log can be viewed either via
the below parameters or by pressing [Alarm Log] on the
keypad and select Fire mode log. It is not possible to reset
the fire mode log.
LG-10 FireMode Log:Event
Range:
0
[0 - 255] This parameter contains an array with 10
*
LG-11 Fire Mode Log: Time
Range:
0 s
[0 - 2147483647
*
s]
03/2016 All rights reserved.
Function:
NOTICE
The frequency converter has no back-up of
the clock function, and the set date/time
resets to default (2000-01-01 00:00) after a
power-down unless an Analog I/O Option
Module with Real Time Clock Battery Back
Up (OPCAIO) is installed. In
parameter K-79 Clock Fault it is possible to
program a warning in case the clock has not
been set properly, for example after a
power-down. Incorrect setting of the clock
affects the time stamps for the maintenance
events.
Function:
elements. The number read represent an error
code, which corresponds to a specific alarm. This
can be found in the Troubleshooting section in the
design guide.
Function:
This parameter contains an array with
10 elements. The parameter shows at
which time the logged event occurred.
Time is measured in seconds since the
first start of the motor.