3.14 BN-## BACnet

3.14.1 BN-7# BACnet
NOTICE
Parameters in this group are active only when
parameter O-30 Protocol is set to [5] BACnet.
BN-70 BACnet Device Instance
Range:
Function:
NOTICE
1
[0 - 4194302]
*
This parameter is active only when
parameter O-30 Protocol is set to [9]
Drive Option.
Enter a unique ID number for the BACnet
device.
BN-72 MS/TP Max Masters
Range:
Function:
127
[1 - 127] Define the address of the master which holds
*
the highest address in this network. Decreasing
this value optimises polling for the token.
BN-73 MS/TP Max Info Frames
Range:
Function:
1
[1 - 65534] Define how many info/data frames the device is
*
allowed to send while holding the token.
BN-74 "I-Am" Service
Option:
Function:
[0]
Send at power-
*
up
[1]
Continuously
Select whether the device should send the
"I-Am" service message only at power-up,
or continuously with an interval of approx-
imately 1 minute.
BN-75 Initialization Password
Range:
Function:
1
[1 - 20] Enter the password needed for execution of Drive
*
Re-initialisation from BACnet.