Parameter Description
AP-26 Dry Pump Function
Select the action for dry pump operation.
Option:
[2]
Alarm
3
3
[3]
Man.
Reset
Alarm
[4]
Stop and
Trip
AP-27 Dry Pump Delay
Range:
10 s
[0 -
*
600 s]
3.19.2 AP-3# No-flow Power Tuning
If auto set-up is disabled in parameter AP-20 Low Power
Auto Set-up, the tuning sequence is:
1.
Close the main valve to stop flow.
2.
Run with motor until the system has reached
normal operating temperature.
3.
Press [Hand] and adjust speed for approximately
85% of rated speed. Note the exact speed.
4.
Read power consumption either by looking for
actual power in the data line in the keypad or by
viewing 1 of the following parameters:
4a
4b
Note the power readout.
5.
Change speed to approximately 50% of rated
speed. Note the exact speed.
6.
Read power consumption either by looking for
actual power in the data line in the keypad or by
viewing 1 of the following parameters:
6a
128
Function:
The frequency converter stops running and
activates a dry-pump alarm (alarm 93, Dry
pump). A frequency converter digital output or a
serial communication bus can communicate an
alarm to other equipment.
The frequency converter stops running and
activates a dry-pump alarm (alarm 93, Dry
pump). A frequency converter digital output or a
serial communication bus can communicate an
alarm to other equipment.
Function:
Defines for how long the dry-pump condition
must be active before activating a warning or an
alarm.
The frequency converter waits for the no-flow
delay time (parameter AP-24 No-Flow Delay) to
expire before the timer for the dry-pump delay
starts.
Parameter DR-10 Power [kW].
or
Parameter DR-11 Power [hp] in the Main
Menu.
Parameter DR-10 Power [kW].
Note the power readout.
7.
Program the speeds used in:
8.
Program the associated power values in:
9.
Switch back with [Auto] or [Off].
NOTICE
Set parameter H-43 Torque Characteristics before tuning
takes place.
AP-30 No-Flow Power
Range:
0 kW
[0 - 0 kW] Readout of calculated no-flow power at
*
AP-31 Power Correction Factor
Range:
100 %
[1 -
400 %]
*
AP-32 Low Speed [RPM]
Range:
0 RPM
[0 - par.
*
AP-36
RPM]
03/2016 All rights reserved.
or
6b
Parameter DR-11 Power [hp] in the Main
Menu.
7a
Parameter AP-32 Low Speed [RPM].
7b
Parameter AP-33 Low Speed [Hz].
7c
Parameter AP-36 High Speed [RPM].
7d
Parameter AP-37 High Speed [Hz].
8a
Parameter AP-34 Low Speed Power [kW].
8b
Parameter AP-35 Low Speed Power [HP].
8c
Parameter AP-38 High Speed Power [kW].
8d
Parameter AP-39 High Speed Power [HP].
Function:
actual speed. If power drops to the display
value, the frequency converter considers the
condition as a no-flow situation.
Function:
Make corrections to the calculated power in
parameter AP-30 No-Flow Power.
If no-flow is detected when it should not be
detected, decrease the setting. However, if no-
flow is not detected when it should be
detected, increase the setting to above 100%.
Function:
To be used if parameter K-02 Motor Speed
Unit is set to [0] RPM (parameter not visible
if [1] Hz is selected).
Set used speed for the 50% level.
This function is used for storing values
necessary for tuning no-flow detection.