Parameter Description
AO-42 Terminal X42/7 Max. Scale
Range:
100
[0 -
%
200 %
*
]
3
3
AO-43 Terminal X42/7 Bus Control
Range:
0 %
[0 - 100 %] Holds the level of terminal X42/7 if
*
AO-44 Terminal X42/7 Timeout Preset
Range:
0 %
[0 -
*
100 %]
3.10.6 AO-5# Analog Out X42/9
AO-50 Terminal X42/9 Output
Option:
[0]
No operation
*
[100] Output
frequency
[101] Reference
[102] Feedback
[103] Motor Current
[104] Torque rel to
limit
[105] Torq relate to
rated
92
Function:
Scale the maximum output of the selected analog
signal at terminal X42/7. Set the value to the
maximum value of the voltage signal output.
Scale the output to give a voltage lower than 10
V at full scale; or 10 V at an output below 100%
of the maximum signal value. If 10 V is the
required output current at a value between 0–
100% of the full-scale output, program the
percentage value in the parameter, that is
50%=10 V. If a voltage between 0 and 10 V is
required at maximum output, calculate the
percentage as follows:
10V
x 100 %
desired maximum voltage
that is
10V
5V :
× 100 % = 200 %
5V
See Illustration 3.28.
Function:
controlled by bus.
Function:
Holds the preset level of terminal X42/7.
If a fieldbus and a time-out function are
selected in parameter AO-50 Terminal X42/9
Output, the output presets to this level.
Function:
Set the function of terminal X42/9.
0–100 Hz, (0–10 V).
Minimum reference–maximum reference,
(0–10 V).
-200% to +200% of
parameter F-53 Maximum Reference, (0–10
V).
0–inverter maximum current
(parameter DR-37 Drive Max. Current), (0–
10 V).
0–torque limit (parameter F-40 Torque
Limiter (Driving)), (0–10 V).
0–motor rated torque, (0–10 V).
AO-50 Terminal X42/9 Output
Option:
[106] Power
[107] Speed
[113] Ext. Closed
Loop 1
[114] Ext. Closed
Loop 2
[115] Ext. Closed
Loop 3
[139] Bus ctrl.
[141] Bus ctrl t.o.
AO-51 Terminal X42/9 Min. Scale
For more information, see parameter AN-51 Terminal 42 Output
Min Scale.
Range:
0 %
[0 -
*
200 %]
AO-52 Terminal X42/9 Max. Scale
See Illustration 3.28.
Range:
100
[0 -
%
200 %]
*
AO-53 Terminal X42/9 Bus Control
Range:
0 %
[0 - 100 %] Holds the level of terminal X42/9 if
*
03/2016 All rights reserved.
Function:
0–motor rated power, (0–10 V).
0 –speed high limit (parameter F-17 Motor
Speed High Limit [RPM] and
parameter F-15 Motor Speed High Limit
[Hz]), (0–10 V).
0–100%, (0–10 V).
0–100%, (0–10 V).
0–100%, (0–10 V).
0–100%, (0–10 V).
0–100%, (0–10 V).
Function:
Scale the minimum output of the selected
analog signal at terminal X42/9, as a percentage
of the maximum signal level, example, if 0 V is
required at 25% of the maximum output value,
program 25%. Scaling values up to 100% can
never be higher than the corresponding setting
in parameter AO-52 Terminal X42/9 Max. Scale.
Function:
Scale the maximum output of the selected
analog signal at terminal X42/9. Set the value to
the maximum value of the voltage signal output.
Scale the output to give a voltage lower than 10
V at full scale; or 10 V at an output below 100%
of the maximum signal value. If 10 V is the
required output current at a value between
0-100% of the full-scale output, program the
percentage value in the parameter, that is,
50%=10 V. If a voltage between 0 and 10 V is
required at maximum output, calculate the
percentage as follows:
that is
10V
5V :
× 100 % = 200 %
5V
Function:
controlled by bus.