Parameter Description
T-61 Continuous Bin Data
Range:
Function:
0
[0 -
Array with 10 elements ([0]-[9] below
*
4294967295]
parameter number in display). Press [OK] and
step between elements with [
10 counters with the frequency of
occurrence for the operating variable
monitored, sorted according to the following
intervals:
Counter [0]: 0–<10%.
Counter [1]: 10–<20%.
Counter [2]. 20–<30%.
Counter [3]: 30–<40%.
Counter [4]: 40–<50%.
Counter [5]: 50–<60%.
Counter [6]. 60–<70%.
Counter [7]: 70–<80%.
Counter [8]. 80–<90%.
Counter [9]: 90–<100% or max.
The above minimum limits for the intervals
are the default limits. These can be changed
in parameter T-65 Minimum Bin Value.
Starts to count when the frequency
converter is powered up for the first time. All
counters can be reset to 0 in
parameter T-66 Reset Continuous Bin Data.
T-62 Timed Bin Data
Array [10]
Range:
Function:
0
[0 -
Array with 10 elements ([0]-[9] below
*
4294967295]
parameter number in display). Press [OK] and
step between elements with [
10 counters with the frequency of occurrence
for the operating data monitored sorted
according to the intervals as for
parameter T-61 Continuous Bin Data.
Starts to count at the date/time programmed
in parameter T-63 Timed Period Start, and
stops at the time/date programmed in
parameter T-64 Timed Period Stop. All counters
can be reset to 0 in parameter T-67 Reset
Timed Bin Data.
DET-620D
AF-600 FP™ Programming Guide
T-63 Timed Period Start
Array [10]
Range:
0
[0 -
*
] and [
].
0]
T-64 Timed Period Stop
Range:
0
[0 - 0]
*
] and [
].
T-65 Minimum Bin Value
Range:
0 %
[0 -
100 %
*
]
03/2016 All rights reserved.
Function:
NOTICE
The frequency converter has no back-up of
the clock function and the set date/time is
reset to default (2000-01-01 00:00) after a
power-down unless the Analog I/O option
module (OPCAIO) with Battery Back Up of
the Real Time Clock is installed.
Consequently, the logging is stopped until
date/time is readjusted in
parameter K-70 Date and Time. In
parameter K-79 Clock Fault it is possible to
programme a warning if in case the clock has
not been set properly, for example after a
power-down.
NOTICE
When mounting Analog I/O option , a
battery back-up of the date and time is
included.
Set the date and time at which the trending starts
the update of the timed bin counters.
Date format depends on setting in
parameter K-71 Date Format, and time format on
setting in parameter K-72 Time Format.
Function:
NOTICE
When mounting Analog I/O Option , a
battery back-up of the date and time is
included.
Set the date and time at which the trend analyses
must stop updating the timed bin counters.
Date format depends on the setting in
parameter K-71 Date Format, and time format on the
setting in parameter K-72 Time Format.
Function:
Array with 10 elements ([0]–[9] below parameter
number in display). Press [OK] and step between
elements with [
] and [
].
Set the minimum limit for each interval in
parameter T-61 Continuous Bin Data and
parameter T-62 Timed Bin Data. Example: If selecting
[1] counter and changing setting from 10% to 12%,
[0] counter is based on the interval 0–<12% and [1]
counter on interval 12%–<20%.
3
3