GE Ecomagination AF-600 FP Programming Manual page 106

Fan & pump drive
Table of Contents

Advertisement

Parameter Description
EN-37 COS Inhibit Timer
Range:
Function:
[0–65.535
Read-only change-of-state inhibit timer. If the
ms]
option is configured for COS operation, this inhibit
timer can be configured in the forward open
telegram to prevent that continuously changing
PCD data generates extensive network traffic. The
inhibit time is in ms, 0=disabled.
EN-38 COS Filters
Range:
Function:
[[0-9] Filter 0–9
Change-of-state PCD filters. Sets up a filter
(0000-FFFFhex)]
mask for each word of process data when
operating in COS-mode. Single bits in the
PCDs can be filtered in/out.
EN-40 Status Parameter
Range:
Function:
NOTICE
0
[0 - 0]
*
This parameter is for Modbus TCP only
EN-41 Slave Message Count
Range:
Function:
NOTICE
0
[0 - 0]
*
This parameter is for Modbus TCP only
EN-42 Slave Exception Message Count
Range:
Function:
NOTICE
0
[0 - 0]
*
This parameter is for Modbus TCP only
EN-80 FTP Server
Option:
Function:
[0]
Disabled
Disables the built-in FTP server.
*
[1]
Enabled
Enables the built-in FTP server.
EN-81 HTTP Server
Option:
Function:
[0]
Disabled
*
[1]
Enabled
Enables the built-in HTTP (web) server.
EN-82 SMTP Service
Option:
Function:
[0]
Disabled
*
[1]
Enabled
Enables the SMTP (e-mail) service on the option.
DET-620D
AF-600 FP™ Programming Guide
EN-89 Transparent Socket Channel Port
Range:
0
[0–9999] Configures the TCP port-number for the
*
EN-90 Cable Diagnostic
Option:
[0]
Disabled
*
[1]
Enabled
EN-91 Auto Cross-Over
Option:
[0]
Disable Disables the auto cross-over function.
[1]
Enable Enables the auto cross-over function.
*
EN-92 IGMP Snooping
Option:
[0]
Disable Disables the IGMP snooping function.
[1]
Enable Enables the IGMP snooping function.
*
EN-93 Cable Error Length
Range:
0
[0 -
*
65535]
03/2016 All rights reserved.
Function:
transparent socket channel. This enables Drive-
messages to be sent transparently on Ethernet via
TCP. Default value is 4000, 0 means disabled.
Function:
NOTICE
The cable diagnostics function is only
issued on ports where there is no link (see
parameter EN-10 Link Status, Link Status)
Enables/disables advanced cable diagnosis
function. If enabled, the distance to cable errors
can be read out in parameter EN-93 Cable Error
Length. The parameter resumes to the default
setting of disable after the diagnostics have
finished.
Function:
NOTICE
Disabling of the auto cross-over function
requires crossed Ethernet cables for daisy-
chaining the options.
Function:
This prevents flooding of the Ethernet protocol
stack by only forwarding multicast packets to ports
that are a member of the multicast group.
Function:
If cable diagnostics is enabled in
parameter EN-90 Cable Diagnostic, the built-in
switch is possible via time domain reflectometry
(TDR). This measurement technique detects
common cabling problems such as open circuits,
short circuits, and impedance mismatches or
breaks in transmission cables. The distance from
the option to the error is shown in meters with an
accuracy of ±2 m. The value 0 means that no
errors are detected.
3
3
105

Advertisement

Table of Contents
loading

Table of Contents