Brocade Communications Systems MLX Series Hardware Installation Manual page 165

Hide thumbs Also See for MLX Series:
Table of Contents

Advertisement

1. Use a #1 Phillips screwdriver to remove the two screws that hold the transparent cover over
FIGURE 99
1
Screws holding transparent cover
2. Use a #2 Phillips screwdriver to remove the power lugs, as shown in
3. Crimp #8 AWG power supply wire into the power lugs and reconnect the lugs to the power
CAUTION
For the NEBS-compliant installation of a NetIron XMR 4000, 8000, and 16000 routers with AC
and DC systems, use a ground wire of at least 6 American Wire Gauge (AWG). The ground wire
should have an agency-approved crimped connector (provided with the device) attached to one
end, with the other end attached to building ground. The connector must be crimped with the
proper tool, allowing it to be connected to both ground screws on the enclosure. Before crimping
the ground wire into the provided ground lug, insure the bare copper wire has been cleaned and
antioxidant is applied to the bare wire.
CAUTION
To ensure adequate bonding when attaching the ground lug, a minimum of 20 PSI of torque is
required to be applied to the mounting hardware used to attach the ground lug.
FIGURE 100
Brocade MLX Series and NetIron XMR Hardware Installation Guide
53-1003821-01
the power supply lugs, as shown in
The NetIron XMR 4000 DC power supply
2
1
1
supply unit.
Crimping the power supply wire in the lug
Installing a NetIron XMR 4000 router
Figure
99. Remove the transparent cover.
2
Screws holding power lugs
3
Figure
99.
149