Drive commissioning (SIMODRIVE)
10.1 SIMODRIVE 611 universal/E, POSMO CD/CA and SI
10.1.5
Setting the access interface
Parameter assignment
The access interface through which SimoCom U accesses the drives connected to
PROFIBUS by means of routing, must be parameterized as follows:
● Access point of the application
The interface can be parameterized directly from SimoCom U. To do so, proceed as follows:
1. Start SimoCom U via the WINDOWS taskbar:
2. In SimoCom U, open the interface dialog using the menu command:
SimoCom U dialog box: Beginning
Dialog: Interface
PG/PC interface dialog box: Beginning
Dialog: Setting the PG/PC interface
PG/PC interface dialog box: End
If SOFTMC cannot be selected for the interface parameterization, the interface has to be
installed first.
OK
Finally, the routing information must be set in the interface dialog of SimoCom U.
350
S7ONLINE STEP7 --> SOFTMC
Start > Programs > SimoComU > SimoComU
Tools > Communication
Radio button: "Route through S7-CPU" ⊙
Button: "Set PG/PC interface..."
Tab: Access path
Access point of the application:
S7ONLINE STEP7 --> SOFTMC
Interface parameter assignment used:
SOFTMC
Button: "Select..."
Dialog: Install/remove interface
Selection: SOFTMC
Button: "Install-->"
Close
Commissioning Manual, 05/2008, 6FC5397–4CP10–4BA0