PROFIBUS DP Communication
8.10 DP slave SIMODRIVE drives
For configuring the drive within the framework of the NC commissioning, please refer to
Subsection "Drive configuration" (Page 389).
② DP master
The information regarding the individual DP slaves are known to the DP masters from the
PROFIBUS SDB generated from the configuration.
DP master transfers the data to/from the DP slaves in isochronous cycles using the following
information:
● PROFIBUS address 10:
● Message frame type 102
For a 2 axis-closed-loop control module of a SIMODRIVE 611 universal, the following
assignment applies:
● Slot 5/6 => Axis 1 or Drive A
● Slot 9/10 => Axis 2 or Drive B
③ DP slave 611U
DP slave interprets the message frames received from the DP master because of the
message frame type 102 set in the following drive parameters:
● Parameter P0922 (PROFIBUS message frame type selection)
304
Setpoint: Slot 5, I/O address 4100
Actual value: Slot 6, I/O address 4100
Setpoint: Slot 9, I/O address 4140
Actual value: Slot 10, I/O address 4140
Commissioning Manual, 05/2008, 6FC5397–4CP10–4BA0
Manual