Drive commissioning (SIMODRIVE)
10.1 SIMODRIVE 611 universal/E, POSMO CD/CA and SI
10.1.3

Setting a PROFIBUS address (SIMODRIVE 611 universal/E)

For SimoCom U to be able to enter online operation with the SIMODRIVE drives connected
to the PROFIBUS, the PROFIBUS address specified in the S7 project (see Chapter "Create
SIMATIC S7 Project" (Page 160)) must be set on DP slave 611U or UE in question using the
display and operator unit.
Figure 10-1
Requirements
The precondition for setting the PROFIBUS address on the control unit is that no faults or
warnings are displayed.
If faults or warnings are displayed (display: E_xxxx), press the "-" key to switch from the
alarm mode to parameterization mode.
Sequence of operations
To set the PROFIBUS address, proceed as follows:
1. Setting the PROFIBUS address (parameter P0918)
2. Saving the PROFIBUS node address in the FEPROM
3. Execute a POWER-ON RESET
348
Display and operator unit
– Hold down key "P" longer than 3 seconds.
=> The current value of the parameter P0918 (PROFIBUS address) is displayed.
– Use keys "+" and "-" to set the desired PROFIBUS address.
– Press "P" again to quit the input mode.
– Press the "+" or "-" key
=> Parameter P0652 (acceptance into FEPROM) is displayed
– Press "P" again to call the input mode.
– Use the "+" key to change the value to 1 (start writing) and wait until the write process
is acknowledged with 0 on the display.
– Push the "POWER ON-RESET" button on the front panel of the drive module.
=> After power-up, the set PROFIBUS address is active.
+
P
-
Commissioning Manual, 05/2008, 6FC5397–4CP10–4BA0
Display
Control unit
Manual