Wiring
6.3.1.3

Isolating transformer

The servo amplifier can also be operated via an isolating transformer when:
}
Protection against indirect contact is absolutely essential, despite a higher leakage cur-
rent
}
An alternative method of contact protection is sought.
For details of how to connect the isolating transformer, please see the section under "Wir-
ing".
6.3.2

Connection cables

We recommend the following cable cross sections in accordance with EN 60204:
Connection
Mains voltage
AC
DC intermediate
circuit
Brake resistor
Motor cables
Resolver,
thermal switch,
max.50 m*
Encoder,
thermal switch,
Max. 50 m*
Incremental en-
coder, thermal
switch,
Max. 25 m
Analogue inputs,
AGND, max
30 m
Digital inputs
and outputs,
BTB, DGND,
max. 30 m
Operating Manual PMCprotego D.48, PMCprotego D.72
1001735-EN-04
INFORMATION
We recommend that the cables between the transformer and the servo
amplifier be kept as short as possible.
Pin designation Device
X0
X8
X8
X8
X2
X1
X1
X3
X3
Cable cross
section
48 A
16 mm²
72 A
25 mm²
48 A
25 mm²
72 A
25 mm²
48 A
35 mm²
72 A
35 mm²
48 A
16 mm²
72 A
25 mm²
All
0.25 mm²
All
0.25 mm²
All
0.25 mm²
All
0.25 mm²
Max. 1.5 mm²
All
0.5 mm²
Max. 1.5 mm²
Conditions
600 V
1000 V, shielded
for lengths > 500
mm
1000 V, shielded
for lengths
> 20 cm
600 V, shielded,
C < 150 pF/m
Twisted pair,
shielded,
C < 120pF/m
Twisted pair,
shielded
Twisted pair,
shielded
Twisted pair,
shielded
103