4.7 Setting standard CPU parameters

4.7.1 Parametrization via Siemens CPU

Parametrization via Sie-
mens CPU 314-6EH04

4.7.2 Parameter CPU

Supported parameters
General
HB400 | CPU | M13-CCF0000 | en | 16-47
5.
Transfer your project.
1
Ethernet PG/OP channel
Since the CPU from VIPA is to be configured as Siemens CPU 314C-2 PN/DP
(314-6EH04-0AB0 V3.3) in the Siemens hardware configurator, the standard parameters
of the VIPA CPU may be set with "Object properties" of the CPU 314C-2 PN/DP during
hardware configuration. Via a double-click on the CPU 314C-2 PN/DP the parameter
window of the CPU may be accessed. Using the registers you get access to every
standard parameter of the CPU.
The CPU does not evaluate each parameter, which may be set at the hardware configu-
ration. The parameters of the following registers are not supported: Synchronous cycle
interrupts, communication and web. The following parameters are currently supported:
n
Short description
The short description of the Siemens CPU is CPU 314C-2 PN/DP
(314-6EH04-0AB0 V3.3).
Order No. / Firmware
n
Order number and firmware are identical to the details in the "hardware catalog"
window.
n
Name
The Name field provides the short description of the CPU.
If you change the name the new name appears in the Siemens SIMATIC Man-
ager.
Deployment CPU M13-CCF0000
Setting standard CPU parameters > Parameter CPU