Deployment CPU M13-CCF0000

Hardware configuration - System MICRO modules

4.5 Hardware configuration - System MICRO modules
System SLIO backplane
bus
Proceeding
60
9.
Navigate in the hardware catalog to the directory 'PROFINET IO
è Additional field devices è I/O è VIPA MICRO PLC' and connect the IO device
M13-CCF0000 to your PROFINET system.
ð In the slot overview of the PROFINET IO device 'VIPA MICRO PLC' the CPU is
already placed at slot 0.
To connect System SLIO modules, the CPU has a backplane bus, which is supplied by
the CPU. Here up to 8 System MICRO modules can be connected.
1.
Perform, if not already done, a hardware configuration for the CPU.
'Hardware configuration - CPU' on page 58
2.
Starting with slot 1 place in the slot overview of the PROFINET IO device 'VIPA
MICRO PLC' your System MICRO modules in the plugged sequence.
3.
Parametrize if necessary the modules and assign valid addresses, so that they can
directly be addressed.
VIPA System MICRO
HB400 | CPU | M13-CCF0000 | en | 16-47
Ä Chapter 4.4