Deployment I/O periphery
Frequency measurement > Parametrization

5.7.3 Proceeding

Hardware configuration
User program

5.7.4 Parametrization

5.7.4.1
Address assignment
Sub module
Input address
Counter
816
820
824
828
Sub module
Output address
Counter
816
820
824
828
5.7.4.2
Interrupt selection
120
In the Siemens SIMATIC Manager the following steps should be executed:
1.
Perform a hardware configuration for the CPU.
tion - CPU' on page 58
2.
Double-click the counter sub module of the CPU 314C-2 PN/DP.
ð The dialog 'Properties' is opened.
3.
As soon as you select the operating mode for the corresponding channel, a dialog
box with default values for this counter mode is created and shown. Select for the
corresponding channel the operating mode 'Frequency counting' .
'Counter operating modes' on page 104
4.
Perform the required parameter settings.
5.
Safe your project with 'Station è Safe and compile'.
6.
Transfer your project to your CPU.
n
The SFB 48 should cyclically be called (e.g. OB 1) for controlling the frequency meas-
urement.
n
The SFB is to be called with the corresponding instance DB. Here the parameters of
the SFB are stored.
Access
DINT
DINT
DINT
DINT
Access
DWORD
DWORD
DWORD
DWORD
Via 'Basic parameters' you can reach 'Select interrupt' . Here you can define the inter-
rupts the CPU will trigger. The following parameters are supported:
n
None: The interrupt function is de-activated.
n
Process: The following events of the frequency measurement can trigger a hardware
interrupt (selectable via 'Frequency counting' ):
End of measurement
Diagnostics and process: A diagnostics interrupt is only triggered when a hardware
n
interrupt was lost.
Ä Chapter 4.4 'Hardware configura-
Assignment
Channel 0: Counter value / Frequency value
Channel 1: Counter value / Frequency value
Channel 2: Counter value / Frequency value
Channel 3: Counter value / Frequency value
Assignment
reserved
reserved
reserved
reserved