YASKAWA VIPA System MICRO M13-CCF0000 Manual page 121

Table of Contents

Advertisement

VIPA System MICRO
5.7.4.3
Operating mode per channel
Parameter hardware con-
figuration
5.7.4.4
Frequency measurement
Parameter hardware con-
figuration
Parameter overview
Operating parameters
Integration time
max. counting frequency...
Hardware interrupt
End of measurement
HB400 | CPU | M13-CCF0000 | en | 16-47
Select via 'Channel' the channel select via 'Operating' the operating mode. The fol-
lowing operating modes are supported:
Not parameterized: Channel is deactivated
n
Ä Chapter 5.6.5.1 'Count continuously' on page 104
n
Ä Chapter 5.6.5.2 'Count once' on page 105
n
Ä Chapter 5.6.5.3 'Count periodically' on page 108
n
Ä Chapter 5.7 'Frequency measurement' on page 117
n
Ä Chapter 5.8 'Pulse width modulation - PWM' on page 123
n
Depending on the selected operating mode default values are loaded and shown in an
additional register.
Default values and structure of this dialog box depend on the selected 'Operating mode' .
The following parameters are supported:
1
Integration time
2
Counting pulse
3
SW gate
4
Evaluated frequency
Description
Specify the integration time
Range of values: 10ms ... 10000ms in steps of 1ms
Specify the max. Frequency for the corresponding input
Range of values: 1, 2, 5, 10, 30, 60kHz
Description
Hardware interrupt at end of measurement
Deployment I/O periphery
Frequency measurement > Parametrization
Assignment
100ms
60kHz
Assignment
de-activated
121