YASKAWA VIPA System MICRO M13-CCF0000 Manual page 62

Table of Contents

Advertisement

Deployment CPU M13-CCF0000
Hardware configuration - Ethernet PG/OP channel
Assign IP address param-
eters
Take IP address parame-
ters in project
62
You get valid IP address parameters from your system administrator. The assignment of
the IP address data happens online in the Siemens SIMATIC Manager starting with ver-
sion V 5.3 & SP3 with the following proceeding:
1.
Start the Siemens SIMATIC Manager and set via 'Options
è Set PG/PC interface'the access path to 'TCP/IP -> Network card ....' .
2.
Open with 'PLC è Edit Ethernet Node n' the dialog window with the same name.
3.
To get the stations and their MAC address, use the [Browse] button or type in the
MAC Address. The Mac address may be found at the 1. label beneath the front flap
of the CPU.
4.
Choose if necessary the known MAC address of the list of found stations.
5.
Either type in the IP configuration like IP address, subnet mask and gateway.
6.
Confirm with [Assign IP configuration].
ð Direct after the assignment the Ethernet PG/OP channel may be reached online
by these address data. The value remains as long as it is reassigned, it is over-
written by a hardware configuration or an factory reset is executed.
1.
Open the Siemens hardware configurator and configure the Siemens CPU 314C-2
PN/DP (314-6EH04-0AB0 V3.3).
2.
For the Ethernet PG/OP channel you have to configure at slot 4 a Siemens CP
343-1 (SIMATIC 300 \ CP 300 \ Industrial Ethernet \CP 343-1 \ 6GK7 343-1EX21
0XE0 V1.2).
3.
Open the property window via double-click on the CP 343-1EX21 and enter for the
CP at 'Properties' the IP address data, which you have assigned before.
4.
Assign the CP to a 'Subnet' . Without assignment the IP address data are not used!
VIPA System MICRO
HB400 | CPU | M13-CCF0000 | en | 16-47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents