Deployment I/O periphery
Pulse width modulation - PWM > Proceeding

5.8.2 Wiring

5.8.2.1
Pulse width modulation outputs
X2: DO byte 0
X2
Function
1
DO 0.7
2
DO 0.6
3
DO 0.5
4
DO 0.4
5
DO 0.3
6
DO 0.2
7
DO 0.1
8
DO 0.0
9
0 V
10
DC 24V

5.8.3 Proceeding

Hardware configuration
124
Type
LED
O
green
O
green
O
green
O
green
O
green
O
green
O
green
O
green
I
red
I
green
In the Siemens SIMATIC Manager the following steps should be executed:
1.
Perform a hardware configuration for the CPU.
tion - CPU' on page 58
2.
Double-click the counter sub module of the CPU 314C-2 PN/DP.
ð The dialog 'Properties' is opened.
3.
As soon as you select the operating mode for the corresponding channel, a dialog
box with default values for this counter mode is created and shown. Select for the
corresponding channel the operating mode 'Pulse width modulation - PWM' .
Ä Chapter 5.6.5 'Counter operating modes' on page 104
4.
Perform the required parameter settings.
5.
Safe your project with 'Station è Safe and compile'.
6.
Transfer your project to your CPU.
Description
Digital output DO 7
Digital output DO 6
Digital output DO 5
Digital output DO 4
Digital output DO 3 / Output channel counter 3
Digital output DO 2 / Output channel counter 2
Digital output DO 1 / PWM 1 / Output channel counter 1
Digital output DO 0 / PWM 0 / Output channel counter 0
4M: GND for onboard DO power section supply / GND
PWM
LED (red) is on at short circuit respectively overload
4L+: DC 24V for onboard DO power section supply
Ä Chapter 4.4 'Hardware configura-
HB400 | CPU | M13-CCF0000 | en | 16-47